Datasheet

Installation5RMI0-02A
105
Inverter Single
According to the confirmation of the above conditions,
prepare the wiring as follows.
1 Never fail to have an individual power circuit
specifically for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the
inside of control cover.
2 The screw which fasten the wiring in the casing of
electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the
course of transportation. Check them and make sure
that they are all tightly fastened. (If they are loose, it
could cause burn-out of the wires.)
3 Specification of power source.
4 Confirm that electrical capacity is sufficient.
5 See that the starting voltage is maintained at more
than 90 percent of the rated voltage marked on the
name plate.
6 Confirm that the cable thickness is as specified in the
power source specification. (Particularly note the
relation between cable length and thickness.
7 Always install an earth leakage circuit breaker in a wet
or moist area.
8 The following would be caused by voltage drop.
- Vibration of a magnetic switch, which will damage
the contact point, fuse breaking, disturbance of the
normal function of the overload.
9 The means for disconnection from a power supply
shall be incorporated in the fixed wiring and have an
air gap contact separation of at least 3mm in each
active(phase) conductors.
CAUTION
Provide the circuit breaker between power source and
the unit as shown by
CAUTION
Cord clamp
Terminal block
Wiring
diagram
Tubing
cover
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breake
or time delay fuse.