Datasheet
Installation5RMI0-02A
103
Inverter Single
2 Align the center of the pipings and
sufficiently tighten the flare nut by hand.
3 Finally, tighten the flare nut with torque wrench until
the wrench clicks.
- When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow
on the wrench.
Gas side piping
(Bigger diameter)
Liquid side piping
(Smaller diameter)
Torque wrench
Outdoor unit
1 Remove the tubing cover from the unit by loosening
the screw.
Tubing cover
mm inch kgf·cm N·m
Ø6.35 1/4 180~250 17.6~24.5
Ø9.52 3/8 340~420 33.3~41.2
Ø12.7 1/2 550~660 53.9~64.7
Ø15.88 5/8 630~820 61.7~80.4
Outside Diameter Torque