Europe Inverter Single Wall Mounted 50Hz/R410A 5RMI0-02A
5RMI0-02A Inverter Single-50Hz (R410A) 1. Models Line up........................................................................................................6 2. Nomenclature ..........................................................................................................8 3. Specifications..........................................................................................................9 4. Dimensional drawings.............................................................................
5RMI0-02A Publication history Plb.
5RMI0-02A Test condition of international standard KSC 9306 ISO 5151 AHRI 210/240 AHAM AS 1861.1 SSA 385 DB°C(°F) 27.0 27.0 26.7(80) 26.7(80) 27.0 29.0 WB°C(°F) 19.5 19.0 19.4(67) 19.4(67) 19.0 19.0 DB°C(°F) 35.0 35.0 35.0(95) 35.0(95) 35.0 46.0 WB°C(°F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0 DB°C(°F) 20.0 20.0 21.1(70) 21.1(70) 21.0 21.0 WB°C(°F) 15.0 15.0 15.6(60) 15.6(60) 15.0 15.5 DB°C(°F) 7.0 7.0 8.3(47) 8.3(47) 7.0 7.0 WB°C(°F) 6.0 6.0 6.
RMI0-02A General Description Split system type air conditioners are known by the category name of Wall Mounted Type systems. The indoor and outdoor unit can be easily installed in a small space and have exceptional cooling capacity. Designed for low-noise operation, these systems ensure a pleasant air conditioned environment. LG offers various types of units to its customers to satisfy various applications and requirements.
Models Line up 5RMI0-02A 1. Models Line up 1.1 Indoor Unit Model names kW(kBtu/h) Type 2.5(9) 3.5(12) ASNW0963WB0 (G09WL) ASNW1263WB0 (G12WL) ASNW096MMS3(H09AK) ASNW126MMS3(H12AK) ASNW096BNR3(D09AK) ASNW126BNR3(D12AK) 5.2(18) 6.
5RMI0-02A Models Line up 1.2 Outdoor Unit Heat pump Total capacity index of connectable indoor units kW kBtu/h ASUW0963WB0(G09WL) ASUW096MUF3(H09AK) ASUW096BUS3(S09AK) ASUW096NRR0(A09LL) ASUW1263WB0(G12WL) ASUW126MUF3(H12AK) ASUW126BUS3(S12AK) ASUW126NRR0(A12LL) 2.5 9 3.5 12 1Ø , 220-240V, 50Hz Power supply Chassis 5.0 18 UL2 Heat pump Total capacity index of connectable indoor units kW kBtu/h ASUW186CRR4(A18RL) ASUW2462EF0(P24EL) ASUW2462WR0(D24RL) 5.2 18 6.
Nomenclature 5RMI0-02A 2.
5RMI0-02A Specifications 3. Specifications Models Heat transfer (sorce / sink) Type of appliance Cooling Capacity Heating Capacity Low Temp.
Specifications 5RMI0-02A kW kW kW W A A A W/W W/W AS-W2462EF0(P24EL) AS-W2462WR0(D24RL) Air to Air Cooling/Heating (Inverter heatpump) 6.8 8.0 4.85 2,193 / 2,285 10.0 / 10.2 10.0 / 10.2 10.6 / 11.0 6.1 3.8 - A++ / A kWh Ø / V / Hz m³/min m³/min l/h dB(A)±3 dB(A)±3 dB(A)±3 dB(A)±3 g g/m W W A N x mm² N x mm² mm mm mm mm mm kg kg °C °C m m 391 / 2,027 1 / 220-240 / 50 24 50 2.5 45 / 40 / 35 /29 54 65 70 R410A, 1,350 35 GKT176MFA Brushless DC Motor Cross Flow Fan BLDC 76 Propeller, Fan BLDC 85 25 3*2.
5RMI0-02A Specifications MODELS Cooling Capacity Heating Capacity Power Input Running Current Starting Current EER SEER COP SCOP Power Supply Power Factor Air Flow Rate Moisture Removal Cooling/Heating Cooling/Heating Cooling/Heating Indoor,H/M/L, Cooling (Heating) Outdoor,Max kW kW W A A W/W W/W W/W W/W Ø / V / Hz % m3/min m3/min Kg/h dB(A)+3 dB(A)+3 g g/m Indoor,H/M/L/S-Low, Cooling (Heating) Outdoor,Max Refrigerant & Charge(at 7.
Specifications Models Heat transfer (sorce / sink) Type of appliance Cooling Capacity Heating Capacity Low Temp.
5RMI0-02A Specifications kW kW kW W A A A W/W W/W AS-W096BWR4(A09WL) AS-W096BRR4(A09RL) Air to Air Cooling/Heating (Invertype heatpump) 2.5 3.2 3.0 670/840 3/3.7 3/3.7 6.5/6 6.2 3.8 AS-W126BWR4(A12WL) AS-W126BRR4(A12RL) Air to Air Cooling/Heating (Invertype heatpump) 3.5 3.8 3.6 1080/1000 4.7/4.4 4.7/4.4 6.5/6 6.1 3.8 - A++/A A++/A kWh 141/1179 201/1400 Ø / V / Hz m3/min m3/min l/h dB(A)±3 dB(A)±3 dB(A)±3 dB(A)±3 g g/m W W A Nⅹmm² Nⅹmm² mm mm mm mm mm kg kg ℃ ℃ m m 1 / 220~240 / 50 12.0 27 1.
Specifications Models Heat transfer (sorce / sink) Type of appliance Cooling Capacity Heating Capacity Low Temp.
5RMI0-02A Model Spec. Heat transfer (sorce / sink) Type of appliance Cooling Capacity Heating Capacity Low Temp.
Specifications 5RMI0-02A kW kW kW W A A A W/W W/W US-W096H4A0(E09EL) US-W096HSA0(Z09SL) Air to Air Cooling/Heating (Invertype heatpump) 2.5 3.2 3.0 690/860 3.1/3.8 3.1/3.8 6.5/6 5.9 3.8 US-W126H4A0(E12EL) US-W126HSA0(Z12SL) Air to Air Cooling/Heating (Invertype heatpump) 3.5 3.8 3.6 1120/1040 4.9/4.6 4.9/4.6 6.5/6 5.8 3.8 - A+/A A+/A kWh 149/1179 211/1400 Ø / V / Hz m3/min m3/min l/h dB(A)±3 dB(A)±3 dB(A)±3 dB(A)±3 g g/m W W A Nⅹmm² Nⅹmm² mm mm mm mm mm kg kg ℃ ℃ m m 1 / 220~240 / 50 12.0 27 1.
5RMI0-02A Model Cooling Capacity Heating Capacity Power Input Running Current Staring Current Max Current SEER SCOP Energy efficiency class* *A(more efficient) G(less efficient) Annual energy consumption Power Supply Air Flow Rate Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Cooling/Heating Inddor, Max Outdoor,Max Moisture Removal Sound Pressure Level Sound Power Level Fan(Indoor) Fan(outdoor) Net Weight Gross Weight Operation Range Max. Piping Length Max.
5RMI0-02A kW kW kW W A A A W/W W/W AS-W1862WR0(D18RL) AS-W1862EF0(P18EL) Air to Air Cooling/Heating (Inverter heatpump) 5.0 5.8 3.8 1,562 / 1,611 7.2 / 7.5 7.2 / 7.5 9.0 / 9.5 6.1 4.0 Cooling/Heating - A++ / A+ Cooling/Heating kWh Ø / V / Hz m³/min m³/min l/h dB(A)±3 dB(A)±3 dB(A)±3 dB(A)±3 g g/m W W A N x mm² N x mm² mm mm mm mm mm kg kg °C °C m m 287 / 1,435 1 / 220-240 / 50 19 32 1.
42 1 30 40 Ø55 Installation Plate 43 Ø55 Place a level on raised tab Unit bottom line 37 287 287 Left rear piping Inverter Single 2 645 37 20 3 Unit outline Right rear piping 645 75 [Unit : mm] 42 121 CHASSIS CODE: S3 - AS-W0963WB0(G09WL) AS-W1263WB0(G12WL) 5RMI0-02A Dimensional drawings 4. Dimensional drawings 4.
47 60 20 Inverter Single Left rear piping Ø65 195 69 Unit Outline 550 Measuring Tape Hanger Installation Plate Measuring Tape Place a level on raised tab 1 1090 3 540 56 325 182 Right rear piping Ø65 2 [Unit : mm] 4 248 47 CHASSIS CODE: S2 ASNW1862EF0(P18EL) ASNW2462EF0(P24EL) ASNW2462WR0(D24RL) ASNW1862WR0(D18RL) Dimensional drawings 5RMI0-02A 52 65 52
50 Inverter Single Left rear piping Ø65 123 175 434 Unit Outline 3 Installation Plate 5 Place a level on raised tab 875 439 217 170 1 295 Ø65 2 Right rear piping 235 4 55 [Unit : mm] 50 CHASSIS CODE : SM ASNW096MMS3(H09AK) ASNW126MMS3(H12AK) 5RMI0-02A Dimensional drawings 21 55
45 55 Ø65 1 Inverter Single 175 133 442 Unit Outline 4 Installation Plate 5 Place a level on raised tab 885 442 3 95 50 59 23 217 159 210 285 Ø65 Right rear piping 2 285 [Unit : mm] 10 50 22 Left rear piping 210 CHASSIS CODE : SB ASNW096BNR3(D09AK) ASNW126BNR3(D12AK) USNW096B8F0(P09RL) USNW126B8F0(P12RL) Dimensional drawings 5RMI0-02A 60 50
45 55 Left rear piping Ø65 1 Inverter Single 133 175 442 Unit Outline 4 Installation Plate 5 Place a level on raised tab 885 442 3 95 217 Right rear piping 285 Ø65 2 45 50 [Unit : mm] 205 CHASSIS CODE : SB ASNW096BWR4(A09WL) ASNW126BWR4(A12WL) ASNW096BRR4(A09RL) ASNW126BRR4(A12RL) 5RMI0-02A Dimensional drawings 23 60
46 64 24 Inverter Single 69 105 Measuring Tape Hanger Measuring Tape Left rear piping 460 Place a level on raised tab Installation Plate Unit Outline Ø65 1 1030 570 3 56 325 (Unit : mm) 207 Right rear piping Ø65 4 2 46 [Unit : mm] 245 CHASSIS CODE : SC ASNW186CRR4(A18RL) Dimensional drawings 5RMI0-02A 52 52
3 Inverter Single Left rear piping Ø70 100 148 Measuring Tape Hanger Installation Plate Measuring Tape Place a level on raised tab Unit Outline 399 399 798 Ø70 145 199 1 292 Right rear piping 2 4 [Unit: mm] 214 CHASSIS CODE : SH USNW096H4A0(E09EL) USNW126H4A0(E12EL) USNW096HSA0(Z09SL) USNW126HSA0(Z12SL) 5RMI0-02A Dimensional drawings 25
4 45 Inverter Single 462 Left Rear 180 Piping 15 228 Unit bottom Line Unit Outline Ø65 1 (Unit : mm) Installation Plate Place a level on raised tab SN CHASSIS 957 3 75 465 229 Right Rear Piping Ø65 305 5 15 6 2 45 55 [Unit: mm] 177 CHASSIS CODE : SN ASNW096NRR0(A09LL) ASNW126NRR0(A12LL) Dimensional drawings 5RMI0-02A 55
210 267 15.79 Inverter Single 545 138 24 277.34 558 770 1 Ø464 106 54 154 70 207 2 3 4 288 [Unit : mm] 5 ASUW0963WB0(G09WL) ASUW096MUF3(H09AK) ASUW126MUF3(H12AK) ASUW096NRR0(A09LL) ASUW1862EF0(P18EL) CHASSIS CODE : UL2 ASUW1263WB0(G12WL) ASUW096BUS3(S09AK) ASUW126BUS3(S12AK) ANUW126NRR0(A12LL) ASUW1862WR0(D18RL) 5RMI0-02A Dimensional drawings 4.
Inverter Single 630 25 28 301 546 870 31 Ø5 54.6 160 340 360 79 1 320 Liquid Pipe Connection Port Control Box Earth Screw 3 4 5 Remark [Unit : mm] CHASSIS CODE: UE 1. The unit should be installed according to installation manual which is in the product box. 2. In an area or a apace having no proper air circulation, an air guide should be installed in the outdoor unit. Note Gas Pipe Connection Port 2 Part Name Air Dicharge Grille 1 No.
Inverter Single 256 234 266 717 462.
Wiring diagrams 5RMI0-02A 5. Wiring diagrams 5.1 Indoor units Models: ASNW0963WB0(G09WL), ASNW1263WB0(G12WL) CN-LR1 CN-LR2 CN-UART CN-UD CN-DISP1 CN-STEP1 CN-EARTH CN-MOTOR CN-SUB CN-POWER CN-STEP2 CN-POWER CN-TH2 CN_EARTH CN-LIGHT How to open the control cover 1. Push the cover to left. 2. Lift up the cover.
5RMI0-02A Wiring diagrams CN1 (CN_LIGHT/CN_DISP1) CN-RECEIVER CN-BOTTOM4 CN-TOP1 CN-TH1 CN-TACT CN-TOP2 CN-STEP2 CN-STEP1 CN-UART CN-BOTTOM3 CN_SW CN_IR Inverter Single 31
Wiring diagrams 5RMI0-02A Models: AS-W1862EF0(P18EL), ASNW2462EF0(P24EL) CN-POWER CN-L/R CN-HVB/UV CN-U/D CN-DISP2 CN-DISP1 CN-12V CN-TH2 CN-TH1 CN-OPTION 32 Inverter Single
5RMI0-02A Wiring diagrams Models: ASNW096MMS3(H09AK),ASNW126MMS3(H12AK) CN-SUB CN-U/D CN-12V CN-STEP_L CN-L/R CN-DISP3 CN-SUB2 CN-SW CN-LIMI CN-HVB CN-DISP1 CN-TH1 CN-TH2 CN-TH3 CN-CN-REMO CN-STEP_R CN-PLASMA CN-SUB1 CN-MOTOR1 Inverter Single CN-DISP2 33
Wiring diagrams 5RMI0-02A Models: ASNW096BNR3(D09AK),ASNW126BNR3(D12AK) CN-SUB CN-U/D CN-DISP3 CN-12V CN-L/R CN-HVB CN-DISP1 CH-TH1 CH-TH2 CH-TH3 CN-CN-REMO CN-MOTOR1 Main PCB 34 Inverter Single
5RMI0-02A Wiring diagrams Models: ASNW096BWR4(A09WL),ASNW126BWR4(A12WL),ASNW096BRR4(A09RL) ASNW126BRR4(A12RL) CN-SUB CN-U/D CN-DISP3 CN-12V CN-L/R CN-DISPLAY CN-TACT CN-MAIN CN-HVB CN-DISP1 CH-TH1 CH-TH2 CH-TH3 CN-CN-REMO CN-LIMIT CN-PLASMA CN-MOTOR1 Main PCB Sub PCB Inverter Single 35
Wiring diagrams 5RMI0-02A Model: ASNW186CRR4(A18RL) RY-COMP(3) CN-U/D CN-L/R RY-COMP(3) CN-DISP3 CN-IN/N CN-HVB CN-DISP1 CN-TH1 CN-TH2 CN-TH3 CN-REMO CN-OPTION 36 Inverter Single
5RMI0-02A Wiring diagrams Models: USNW096B8F0(P09RL),USNW126B8F0(P12RL) MEZ65064706 CN-MOTOR1 CN-HVB CN-U/D WHITE CN-DISP2 CN-DISP1 CN-TH2 CN-TH1 Inverter Single 37
Wiring diagrams 5RMI0-02A Models: USNW096H4A0(E09EL),USNW126H4A0(E12EL),USNW096HSA0(Z09SL) USNW126HSA0(Z12SL) CN-MOTOR1 CN-U/D WHITE CN-DISP2 CN-DISP1 CN-TH2 CN-TH1 38 Inverter Single
5RMI0-02A Wiring diagrams Models: ASNW096NRR0(A09LL), ASNW126NRR0(A12LL) CN_LIMIT CN_POWER CN_MOTOR CN_UD CN_HVPS CN_LR CN_INLET CN_WRITE CN_SCAN CN_DATA CN_TH2 CN_TH1 CN_USP1 CN_UART CN_RECEIVER CN_INLET2 CN_CC CN_TACT CN_IR CN_REMO CN_SW CN_INLET1 CN_USP2 CN_MAIN1 CN_DISP CN_MAIN2 Inverter Single 39
Wiring diagrams 5RMI0-02A Models: AS-W1862WR0(D18RL), AS-W2462WR0(D24RL) CN-OUT/N CN-L1 CN-L/R CN-SUB CN-U/D CN-12V CN-DISP3 CN-HVB CN-DISP1 CN-TH1 CN-TH3 CN-REMO CN-CC CN-OPTION CN-COM 40 Inverter Single CN1
5RMI0-02A Wiring diagrams 5.
Wiring diagrams 5RMI0-02A Model: ASUW2462EF0(P24EL), AS-W2462WR0(D24RL) CN-FAN(DC) CN-TH1 CN-EEV1 CN-4WAY CN-TH2 CN-U_V_W CN-COM P(L)_BR CN-COIL2 42 CN-COIL1 Inverter Single P(N)_BL
5RMI0-02A Wiring diagrams Models: ASUW096MUF3(H09AK),ASUW126MUF3(H12AK) CN-FAN(DC) CN-TH2 DC-4WAY CN-EEV CN-TH1 CN-4WAY CN-4WAY(AC) DC-4WAY-Con CN-4WAY(DC) CN-COIL2 CN-COIL1 Inverter Single 43
Wiring diagrams 5RMI0-02A Models: ASUW096BUS3(S09AK),ASUW126BUS3(S12AK) CN-U(S) CN-V(R) CN-W(C) CN-EEV CN-FAN(DC) CN-TH1 CN-TH2 CN-4WAY CN-COM CN-COIL1 WCN-P(L) CN-3 CN-COIL2 44 CN-2 Inverter Single WCN-P(N)
5RMI0-02A Wiring diagrams Model: ASUW186CRR4(A18RL) CN-FAN(DC) CN-U(S) CN-V(R) CN-W(C) CN-EEV1 CN-TH1 CN-4WAY CN-TH2 CN-COM CN-COIL2 CN-COIL1 Inverter Single 45
Wiring diagrams 5RMI0-02A Models: USUW096B8F0(P09RL),USUW126B8F0(P12RL) CN-TH2 CN-TH1 CN-EEV CN1 CN-4WAY CN-LGMV CN-FAN CN-CENTRAL CN-JTAG CN-FLASH CN-COIL1 WCN-P(L) WCN-P(N) CN-COIL2 46 MAIN PCB Inverter Single
5RMI0-02A Wiring diagrams Models: USUW096H4A0(E09EL),USUW126H4A0(E12EL) CN-TH2 CN-TH1 CN-EEV CN1 CN-LGMV CN-4WAY CN-CENTRAL CN-JTAG CN-FLASH CN-COIL1 WCN-P(L) WCN-P(N) CN-COIL2 MAIN PCB Inverter Single 47
Wiring diagrams 5RMI0-02A Models: ASUW096NRR0(A09LL), ASUW126NRR0(A12LL) CN-U_V_W CN-EEV1 CN-FAN(DC) CN-TH2 CN-TH1 CN-COIL2 48 CN-COIL2 Inverter Single CN-4WAY
5RMI0-02A Wiring diagrams Models: AS-W1862EF0(P18EL), AS-W1862WR0(D18RL) CN-LGMV CN-FAN CN-EEV1 CN-TH1 CN_U_V_W CN-4WAY CN-TH2 CN-COM P(L)_BR CN-COIL1 P(N)_BL CN-COIL2 WCN-GND2 Inverter Single WCN-GND1 49
Refrigerant cycle diagram 5RMI0-02A 6.
5RMI0-02A Refrigerant cycle diagram Models: AS-W1862EF0(P18EL), AS-W2462EF0(P24EL), AS-W1862WR0(D18RL) AS-W2462WR0(D24RL) Indoor Unit Outdoor Unit Liquid Side EEV 2-Way Valve Th1 Th2 Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Th5 Th4 Gas Side Reversing Valve Accumulator 3-Way Valve Th3 Compressor LOC Th1 Th2 Th3 Th4 Th5 Description Thermistor for indoor air temperature Thermistor for evaporating temperature Thermistor for discharge pipe temperature Thermistor for condensing tempe
Refrigerant cycle diagram 5RMI0-02A Models: AS-W096MMS3(H09AK),AS-W126MMS3(H12AK) Indoor Unit Outdoor Unit Liquid Side Th2 EEV 2-Way Valve Th1 Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Th5 Th4 Gas Side 3-Way Valve Reversing Valve Accumulator Th3 Compressor LOC.
5RMI0-02A Refrigerant cycle diagram Models: AS-W096BNR3(D09AK),AS-W126BNR3(D12AK) Indoor Unit Outdoor Unit Liquid Side Th1 Th2 EEV 2-Way Valve Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Th5 Th4 Gas Side 3-Way Valve Reversing Valve Accumulator Th3 Compressor LOC Th1 Th2 Th3 Th4 Th5 Description Thermistor for indoor air temperature Thermistor for evaporating temperature Thermistor for discharge pipe temperature Thermistor for condensing temperature Thermistor for outdoor air tempe
Refrigerant cycle diagram 5RMI0-02A Models: AS-W096BWR4(A09WL),AS-W126BWR4(A12WL),AS-W096BRR4(A09RL) AS-W126BRR4(A12RL) Indoor Unit Outdoor Unit Liquid Side Th1 Th2 EEV 2-Way Valve Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Th5 Th4 Gas Side 3-Way Valve Reversing Valve Accumulator Th3 Compressor LOC Th1 Th2 Th3 Th4 Th5 Description Thermistor for indoor air temperature Thermistor for evaporating temperature Thermistor for discharge pipe temperature Thermistor for condensing temper
5RMI0-02A Refrigerant cycle diagram Model: AS-W186CRR4(A18RL) Indoor Unit Outdoor Unit Liquid Side EEV 2-Way Valve Th2 Th1 Th4 Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Th3 Th7 Th6 Gas Side Reversing Valve Accumulator 3-Way Valve Th5 Cooling Heating Compressor LOC.
Refrigerant cycle diagram 5RMI0-02A Models: US-W096B8F0(P09RL),US-W126B8F0(P12RL) Indoor Unit Outdoor Unit Liquid Side EEV 2-Way Valve Th1 Heat Exchanger (Evaporator) Th2 Heat Exchanger (Condenser) Th5 Th4 Gas Side 3-Way Valve Reversing Valve Accumulator Th3 Cooling Heating Compressor LOC.
5RMI0-02A Refrigerant cycle diagram Models: US-W096H4A0(E09EL),US-W126H4A0(E12EL),US-W096HSA0(Z09SL) US-W126HSA0(Z12SL) Indoor Unit Outdoor Unit Liquid Side EEV 2-Way Valve Th1 Heat Exchanger (Evaporator) Th2 Heat Exchanger (Condenser) Th5 Th4 Gas Side 3-Way Valve Reversing Valve Accumulator Th3 Cooling Heating Compressor LOC.
Refrigerant cycle diagram 5RMI0-02A Models: AS-W096NRR0(A09LL), AS-W126NRR0(A12LL) Indoor Unit Outdoor Unit Liquid Side Th2 EEV 2-Way Valve Th1 Heat Exchanger (Evaporator) Heat Exchanger (Condenser) Th5 Th4 Gas Side Th3 Reversing Valve Accumulator 3-Way Valve Cooling Heating Compressor LOC.
5RMI0-02A Capacity tables 7. Capacity tables 7.1 Cooling Capacity Model: AS-W0963WB0(G09WL) Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 TC 2.45 2.60 2.75 2.83 3.05 3.21 20 SHC 2.31 2.20 2.10 2.06 1.95 1.89 TC 2.04 2.19 2.34 2.41 2.64 2.78 40 SHC 2.41 2.30 2.19 2.15 2.03 1.98 PI 0.43 0.58 0.63 0.64 0.64 0.63 PI 0.74 0.80 0.81 0.81 0.82 0.84 TC 2.34 2.49 2.65 2.72 2.95 3.
Capacity tables 5RMI0-02A Model: AS-W2462EF0(P24EL), AS-W2462WR0(D24RL) Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 TC 6.67 7.08 7.49 7.69 8.31 8.72 20 SHC 6.28 5.99 5.71 5.61 5.30 5.14 TC 5.55 5.96 6.36 6.56 7.17 7.57 40 SHC 6.56 6.26 5.97 5.86 5.53 5.37 PI 1.21 1.64 1.78 1.80 1.80 1.79 PI 2.08 2.24 2.27 2.28 2.32 2.37 TC 6.38 6.79 7.19 7.40 8.01 8.42 Outdoor Air Temperature : °CDB 25 32 SHC PI TC SHC 6.
5RMI0-02A Capacity tables Model: AS-W126MMS3(H12AK) Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 TC 3.43 3.64 3.85 3.96 4.28 4.49 20 SHC 2.95 2.98 3.01 3.04 3.10 3.15 TC 2.86 3.07 3.27 3.38 3.69 3.90 40 SHC 2.56 2.62 2.67 2.71 2.79 2.86 PI 0.43 0.58 0.63 0.64 0.64 0.63 PI 0.74 0.80 0.81 0.81 0.82 0.84 TC 3.28 3.49 3.70 3.81 4.12 4.33 Outdoor Air Temperature : °CDB 25 32 SHC PI TC SHC 2.85 0.45 3.08 2.73 2.
Capacity tables 5RMI0-02A Model: AS-W126BNR3(D12AK) Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 TC 3.43 3.64 3.85 3.96 4.28 4.49 20 SHC 2.95 2.98 3.01 3.04 3.10 3.15 TC 2.86 3.07 3.27 3.38 3.69 3.90 40 SHC 2.56 2.62 2.67 2.71 2.79 2.86 PI 0.49 0.66 0.71 0.72 0.72 0.72 PI 0.84 0.90 0.91 0.92 0.93 0.95 TC 3.28 3.49 3.70 3.81 4.12 4.33 Outdoor Air Temperature : °CDB 25 32 SHC PI TC SHC 2.85 0.51 3.08 2.73 2.
5RMI0-02A Capacity tables Models: AS-W126BWR4(A12WL), AS-W126BRR4(A12RL), US-W126B8F0(P12RL) Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 TC 3.43 3.64 3.85 3.96 4.28 4.49 20 SHC 2.95 2.98 3.01 3.04 3.10 3.15 TC 2.86 3.07 3.27 3.38 3.69 3.90 40 SHC 2.56 2.62 2.67 2.71 2.79 2.86 PI 0.60 0.81 0.87 0.88 0.88 0.88 PI 1.03 1.10 1.12 1.12 1.14 1.17 TC 3.28 3.49 3.70 3.81 4.12 4.
Capacity tables 5RMI0-02A Models: US-W096H4A0(E09EL), US-W096HSA0(Z09SL) Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 TC 2.45 2.60 2.75 2.83 3.05 3.21 20 SHC 2.10 2.13 2.15 2.17 2.21 2.25 TC 2.04 2.19 2.34 2.41 2.64 2.78 40 SHC 1.83 1.87 1.91 1.93 1.99 2.04 PI 0.38 0.52 0.56 0.57 0.57 0.56 PI 0.66 0.71 0.72 0.72 0.73 0.74 TC 2.34 2.49 2.65 2.72 2.95 3.
5RMI0-02A Capacity tables Model : AS-W096NRR0(A09LL) Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 TC 2.45 2.60 2.75 2.83 3.05 3.21 20 SHC 2.10 2.13 2.15 2.17 2.21 2.25 TC 2.04 2.19 2.34 2.41 2.64 2.78 40 SHC 1.83 1.87 1.91 1.93 1.99 2.04 PI 0.32 0.43 0.47 0.48 0.47 0.47 PI 0.55 0.59 0.60 0.60 0.61 0.63 TC 2.34 2.49 2.65 2.72 2.95 3.10 Outdoor Air Temperature : °CDB 25 32 SHC PI TC SHC 2.04 0.33 2.20 1.
Capacity tables 5RMI0-02A Models: AS-W1862EF0(P18EL), AS-W1862WR0(D18RL) Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 Indoor Air Temperature °CWB °CDB 14 20 16 22 18 25 19 27 22 30 24 32 TC 4.90 5.20 5.51 5.66 6.11 6.41 20 SHC 4.21 4.26 4.30 4.34 4.42 4.51 TC 4.08 4.38 4.68 4.83 5.27 5.57 40 SHC 3.66 3.75 3.82 3.87 3.99 4.09 PI 0.86 1.17 1.26 1.28 1.28 1.27 PI 1.48 1.60 1.62 1.62 1.65 1.69 TC 4.69 4.99 5.29 5.44 5.89 6.
5RMI0-02A 7.2 Heating Capacity Model: AS-W0963WB0(G09WL) Indoor Air Temperature °CDB 16 18 20 21 22 24 -15 TC 2.26 2.23 2.22 2.21 2.21 2.18 -10 PI 0.68 0.69 0.70 0.71 0.71 0.73 TC 2.37 2.37 2.37 2.37 2.37 2.35 -5 PI 0.66 0.68 0.69 0.70 0.71 0.73 TC 2.57 2.58 2.58 2.58 2.58 2.54 PI 0.69 0.71 0.73 0.74 0.75 0.77 Outdoor Air Temperature : °CDB 6 10 0 TC PI TC PI TC PI 2.75 0.74 3.05 0.79 3.22 0.83 2.75 0.76 3.03 0.81 3.18 0.84 2.74 0.78 3.00 0.83 3.16 0.86 2.73 0.79 2.98 0.84 3.16 0.86 2.73 0.80 2.
Capacity tables 5RMI0-02A Model: AS-W096MMS3(H09AK) Indoor Air Temperature °CDB 16 18 20 21 22 24 -15 TC 2.41 2.38 2.37 2.36 2.36 2.33 PI 0.57 0.58 0.59 0.60 0.60 0.62 -10 TC 2.53 2.53 2.53 2.53 2.53 2.50 -5 PI 0.56 0.57 0.59 0.59 0.60 0.62 TC 2.74 2.75 2.75 2.75 2.75 2.71 PI 0.58 0.60 0.62 0.63 0.63 0.65 Outdoor Air Temperature : °CDB 0 6 10 TC PI TC PI TC PI 2.93 0.63 3.25 0.67 3.44 0.70 2.93 0.64 3.23 0.69 3.39 0.71 2.92 0.66 3.20 0.70 3.37 0.72 2.92 0.67 3.18 0.71 3.37 0.73 2.91 0.68 3.16 0.
5RMI0-02A Capacity tables Model: AS-W126BNR3(D12AK) Indoor Air Temperature °CDB 16 18 20 21 22 24 -15 TC 3.01 2.98 2.96 2.95 2.94 2.91 PI 0.78 0.79 0.81 0.82 0.83 0.85 -10 TC 3.16 3.16 3.16 3.16 3.16 3.13 -5 PI 0.76 0.78 0.80 0.81 0.83 0.85 TC 3.43 3.43 3.44 3.44 3.43 3.39 PI 0.80 0.82 0.85 0.86 0.87 0.89 Outdoor Air Temperature : °CDB 0 6 10 TC PI TC PI TC PI 3.66 0.86 4.07 0.92 4.30 0.96 3.66 0.88 4.04 0.94 4.24 0.97 3.65 0.91 4.00 0.96 4.21 0.99 3.64 0.92 3.97 0.97 4.21 1.00 3.63 0.93 3.95 0.
Capacity tables 5RMI0-02A Model: AS-W186CRR4(A18RL) Indoor Air Temperature °CDB 16 18 20 21 22 24 -15 TC 4.74 4.69 4.66 4.65 4.64 4.58 PI 1.35 1.37 1.39 1.40 1.42 1.45 -10 TC 4.98 4.98 4.97 4.97 4.98 4.93 -5 PI 1.31 1.35 1.38 1.40 1.42 1.46 TC 5.40 5.41 5.41 5.41 5.41 5.34 PI 1.37 1.41 1.45 1.47 1.49 1.54 Outdoor Air Temperature : °CDB 0 6 10 TC PI TC PI TC PI 5.77 1.48 6.40 1.58 6.77 1.64 5.77 1.52 6.36 1.62 6.68 1.67 5.75 1.56 6.30 1.65 6.64 1.70 5.74 1.58 6.26 1.67 6.64 1.71 5.72 1.60 6.21 1.
5RMI0-02A Capacity tables Model: AS-W096NRR0(A09LL) Indoor Air Temperature °CDB 16 18 20 21 22 24 -15 TC 2.41 2.38 2.37 2.36 2.36 2.33 PI 0.64 0.65 0.66 0.66 0.67 0.69 -10 TC 2.53 2.53 2.53 2.53 2.53 2.50 -5 PI 0.62 0.64 0.65 0.66 0.67 0.69 TC 2.74 2.75 2.75 2.75 2.75 2.71 PI 0.65 0.67 0.69 0.70 0.71 0.73 Outdoor Air Temperature : °CDB 0 6 10 TC PI TC PI TC PI 2.93 0.70 3.25 0.75 3.44 0.78 2.93 0.72 3.23 0.76 3.39 0.79 2.92 0.74 3.20 0.78 3.37 0.80 2.92 0.75 3.18 0.79 3.37 0.81 2.91 0.76 3.16 0.
Capacity coefficient factor 5RMI0-02A 8.
5RMI0-02A Capacity coefficient factor Cooling Capacity(%) 110 105 100 95 9k, 12k 90 85 80 75 70 2 7.5 20 Total Pipe Length(m) Heating 110 Capacity(%) 105 100 9k, 12k 95 90 85 80 75 70 2 7.
Capacity coefficient factor 5RMI0-02A Cooling Capacity(%) 100 18k 24k, 28k 90 80 70 7.5 15 30 50 Total Pipe Length(m) Heating Capacity(%) 100 18k 24k, 28k 90 80 70 7.
5RMI0-02A Operation range 9.
Air flow and temperature distributions 5RMI0-02A 10. Air flow and temperature distributions (reference data) Models: AS-W0963WB0(G09WL), AS-W1263WB0(G12WL) Cooling Heating Discharge angle:60° Discharge angle:60° Air velocity [m/s] Air velocity [m/s] 2m 2m 0.2 1 2.0 .5 1.0 3.0 2.5 7m 6m 5m 4m 3m 2m 6m 5m 4m 3m 2m 0m 0m 1m 18 16 14 6m 5m 4m 3m 2m 2m 2m 1.5m 1.5m 1m 1m 20 22 7m 7m Temperature [°C] Temperature [°C] 8m 0.2 8m 27 29 33 31 8m 1m 0.5 1.0 1.5 1m 2.
5RMI0-02A Air flow and temperature distributions Model: AS-W126MMS3(H12AK) Cooling Heating Discharge angle:160° Discharge angle:110° Air velocity [m/s] Air velocity [m/s] 2m 5.0 4.5 4.0 6m 2.0 1.5 1.0 7m 5m 4m 3m 5.0 4.5 4.0 1m 3.5 8m 2m 3.5 3.0 2.5 2m 1m 0m 0m 1m Temperature [°C] 1.5 7m 8m 6m 5m 2.5 2.0 4m 3m 3.
Air flow and temperature distributions 5RMI0-02A Model: AS-W186CRR4(A18RL) Cooling Heating Discharge angle:135° Discharge angle:120° Air velocity [m/s] Air velocity [m/s] 2m 4.0 3.5 3.0 3.5 1m 2.5 1.0 8m 7m 6m 5m 2.5 2.0 1.5 4m 3m 2m 0m 0m 1m Temperature [°C] 2m 5.5 0 . 4 1.0 8m 7m 2.0 1.5 6m 5m 1m 3.
5RMI0-02A Air flow and temperature distributions Models: AS-W096NRR0(A09LL), AS-W126NRR0(A12LL) Cooling Heating Discharge angle:130° Discharge angle:110° Air velocity [m/s] Air velocity [m/s] 2m 4.0 4.5 5.5 6.0 2m 5.0 4.5 3.5 1m 3.0 8m 7m 6m 5m 2.6 2.5 1.5 4m 3m 2m 1m 4.0 1m 0m 0m Temperature [°C] 8m 7m 6m 5m 1.5 2.0 3.0 3.5 2.
Sound levels 5RMI0-02A 11. Sound levels(Reference data) 11.1 Indoor Units Overall Notes: - Sound measured at 1m away from the center of the unit. - Data is valid at free field condition. - Data is valid at nominal operation condition. - Reference accoustic pressure 0dB=20Pa. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard. 1m 0.
5RMI0-02A Sound levels ASNW096BWR4(A09WL) ASNW096BRR4(A09RL) USNW096B8F0(P09RL) ASNW126BNR3(D12AK) 80 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 Approximate Hearing Threshold 10 63 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 Approximate Hearing Threshold NC-15 250 500 1000 2000 4000 NC-25 20 NC-20 125 80 ▲ High ■ Mid ● Low 10 8000 63 Octave Band Center Frequency (Hz) NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25
Sound levels 5RMI0-02A ASNW096NRR0(A09LL) ASNW126NRR0(A12LL) ASNW1862WR0(D18RL) ASNW1862EF0(P18EL) 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 Approximate Hearing Threshold 10 63 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency (Hz) NC-25 20 Approximate Hearing Threshold NC-20 NC-15 80 ▲ High ■ Mid ● Low 10 63 NC-15 125 250 500 1000 2000 Octave Band Sound Pressure Le
5RMI0-02A Sound levels 11.2 Outdoor Units Overall Notes: - Sound measured at 1m away from the center of the unit. - Data is valid at free field condition. - Data is valid at nominal operation condition. - Reference accoustic pressure 0dB=20Pa. - Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment is installed. - The operating conditions are assumed to be standard.
Sound levels 5RMI0-02A ASUW126BUS3(D12AK) USUW096B8F0(P09RL) NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 Approximate Hearing Threshold 63 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 500 1000 2000 4000 NC-25 20 Approximate Hearing Threshold NC-15 250 ▲ High ■ Mid ● Low 70 NC-20 125 80 10 8000 63 Octave Band Center Frequency (Hz) NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 250 500 1000 2000 4000 63 NC-15 125 250 500
5RMI0-02A ASUW096NRR0(A09LL) 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 Approximate Hearing Threshold 63 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 Approximate Hearing Threshold NC-15 250 500 1000 2000 4000 NC-25 20 NC-20 125 80 ▲ High ■ Mid ● Low 10 8000 63 Octave Band Center Frequency (Hz) NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 63 NC-15 250 500 1000 2000 4000 NC-15 250 500 1000 2000 4000 Octave
5RMI0-02A 86 Inverter Single
5RMI0-02A Remote controller 12. Remote controller Wireless Remote Controller Display Screen P/No: AKB73996601 1 After a while Set et Tem Temp 4 5 Set Temp 18 2 7 18 1 6 °C Room Temp °C 25 °C 3 8 9 • Applied Model : AS-W0963WB0(G09WL) AS-W1263WB0(G12WL) • , , and E are button type and icons on display screen are touch type. • Display screen turns off if untouched for a period of time. ① On/Off button : Turns A/C or display screen on/off.
Remote controller 5RMI0-02A Wireless Remote Controller P/No: AKB73456113 Display screen Control panel Display screen Description A K IONIZER button*: Plasmaster Ionizer sterilize the aerial bacteria and other harmful substances. l Sleep mode auto button*: Sets the sleep mode auto operation. _ Temperature adjustment buttons: Adjusts the room temperature when cooling and heating.
5RMI0-02A Remote controller You can operate the air conditioner more conveniently with the remote control. You will find the buttons for the additional functions bellow the down of the display screen. P/No: AKB73635603 Display screen Control panel Display screen Description A K IONIZER button*: Plasmaster Ionizer sterilize the aerial bacteria and other harmful substances. Sleep mode auto button*: Sets the sleep mode auto operation.
Remote controller 5RMI0-02A You can operate the air conditioner more conveniently with the remote control. You will find the buttons for the additional functions under the cover of the remote control. P/No: AKB73635619 Display screen Control panel Display screen A K IONIZER button*: Plasmaster Ionizer sterilize the aerial bacteria and other harmful substances. Sleep mode auto button*: Sets the sleep mode auto operation.
5RMI0-02A Remote controller You can operate the air conditioner more conveniently with the remote control. You will find the buttons for the additional functions under the cover of the remote control. P/No: AKB73456104 Display screen JET Control panel • Applied Model : USNW096H4A0(E09EL) USNW126H4A0(E12EL) USNW096HSA0(Z09SL) USNW126HSA0(Z12SL) Control panel Display screen Description / 4 Fan button : Air come out from the indoor unit below to the room without air temperature change.
Remote controller 5RMI0-02A You can operate the air conditioner more conveniently with the remote control. P/No: AKB73975605 Display screen Control panel Display screen A K l l _ | g Control panel • Applied Model : ASNW096NRR0(A09LL) ASNW126NRR0(A12LL) o - Description IONIZER button* : Plasmaster Ionizer sterilize the aerial bacteria and other harmful substances. Sleep mode auto button*: Sets the sleep mode auto operation.
5RMI0-02A You can operate the air conditioner more conveniently with the remote control. You will find the buttons for the additional functions under the cover of the remote control. Control panel P/No: AKB73855721 A Display screen A/CLEAN[3SEC] ROOM TEMP IONIZER button*: Plasmaster Ionizer sterilize the aerial bacteria and other harmful substances. Sleep mode auto button*: Sets the sleep mode auto operation. _ Temperature adjustment buttons: Adjusts the room temperature when cooling and heating.
Installation 5RMI0-02A 13. Installation 13.1 AS-W0963WB0(G09WL), AS-W1263WB0(G12WL) Installation Map Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealant) Bend the pipe as closely on the wall as possible, but be careful that it doesn't break. Vinyl tape (Wide) Saddle • Apply after carrying out a drainage test. • To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
5RMI0-02A Installation Select the best Location Indoor unit - There should not be any heat or steam near the unit. - Select a place where there are no obstacles around of the unit. - Make sure that condensation drainage can be conveniently routed away. - Do not install near a doorway. - Ensure that the interval between a wall and the left (or right) of the unit is more than 500mm. The unit should be installed as high as possible on the wall, allowing a minimum of 200mm from ceiling.
Installation 5RMI0-02A Remove the Terminal block cover Preparing Work for Installation 1 Remove the one taptite screw and one ground screw at the right side part. Open the front panel 1 Pull out the lower section of front panel and lift it up. Type C Front panel Ground Screw 2 Detach the terminal block cover. Remove the service cover 1 To detach the SVC cover, pull the two screw covers and remove the two screws at the lower part. 1 2 Detach the clamp 2 Pull down the SVC cover. 1.
5RMI0-02A Installation Fixing installation Plate The wall you select should be strong and solid enough to prevent vibration. Installation Plate 1 Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts. - Mount the installation plate horizontally by aligning the centerline using Horizontal meter . 2 Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate.
Installation 5RMI0-02A Flaring Work Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure. Cut the pipes and the cable 1 Use the piping kit accessory or the pipes purchased locally. 2 Measure the distance between the indoor and the outdoor unit. 3 Cut the pipes a little longer than measured distance. 4 Cut the cable 1.5m longer than the pipe length.
5RMI0-02A Installation Connecting the Piping WARNING Preparing the indoor units piping and drain hose for installation through the wall. 1 Route the indoor tubing and the drain hose in the direction of rear left or right. Drain hose junction 1 Remove the rubber stopple in the desired drain direction. 2 Insert drain hose into the handle of drain pan, and join drain hose and connecting hose according to the figure by. Left Downwards Installation Information. For right piping.
Installation 5RMI0-02A Installation of Indoor Unit Hook the indoor unit onto the upper portion of the installation plate.(engage the two hooks at the top of the indoor unit with the upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it left and right. 3 Tape the tubing pipe, drain hose and the connection cable. Be sure that the drain hose is located at the lowest side of the bundle.
5RMI0-02A Installation Connecting the installation pipe and drain hose to the indoor unit. 1. Align the center of the pipes and sufficiently tighten the flare nut by hand Indoor unit tubing Flare nut Pipes 2. Tighten the flare nut with a wrench Outside Diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Open-end wrench (fixed) Torque kgf·cm N·m 180~250 17.6~24.5 340~420 33.3~41.2 550~660 53.9~64.7 630~820 61.7~80.4 Flare nut Connection pipe Wrench Indoor unit tubing 3.
Installation 5RMI0-02A 4 Finish the assembly by screwing the unit to the installation plate by using two pieces of type "C" screws. Finishing the indoor unit installation 1 Assemble the clamp for piping and screw it up. Clamp 2 Assemble the terminal block cover. 5 Assemble the service cover and screw it up. 3 Screw up the terminal block cover as the initial condition.
5RMI0-02A Installation Outdoor unit 1 Remove the tubing cover from the unit by loosening the screw. Tubing cover 2 Align the center of the pipings and sufficiently tighten the flare nut by hand. 3 Finally, tighten the flare nut with torque wrench until the wrench clicks. - When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. Outside Diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.
Installation 5RMI0-02A Connecting the Cables Indoor Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.) The power connecting cable with indoor and outdoor unit should be selected according to the following national wiring regulations.
5RMI0-02A Installation CAUTION Terminal block Wiring diagram Cord clamp Tubing cover CAUTION Provide the circuit breaker between power source and the unit as shown by Main power source Air Conditioner Circuit Breaker Use a circuit breake or time delay fuse. According to the confirmation of the above conditions, prepare the wiring as follows. 1 Never fail to have an individual power circuit specifically for the air conditioner.
Installation 5RMI0-02A Checking the Drainage To check the drainage. 1 Pour a glass of water on the evaporator. 2 Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. Connecting area drain hose Leakage checking Leakage checking Drain Pan Drain Hose Drain piping 1. The drain hose should point downward for easy drain flow. Downward slope 2. Do not make drain piping like the following.
5RMI0-02A Installation In cases where the Outdoor unit is installed above the Indoor unit perform the following. Forming the Piping Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes. - If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately. 1 Tape the piping and connecting cable from down to up.
Installation 5RMI0-02A Air Purging The air and moisture remaining in the refrigerant system have undesirable effects as indicated below. 1 Pressure in the system rises. 2 Operating current rises. 3 Cooling(or heating) efficiency drops. 4 Moisture in the refrigerant circuit may freeze and block capillary tubing. 5 Water may lead to corrosion of parts in the refrigeration system. Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor unit.
5RMI0-02A Installation Soap water method 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valve. 3. Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. 4. If bubbles come out, the pipes have leakage Liquid side 2-way valve (Close) Gas side Cap Evacuation 1.
Installation 5RMI0-02A Test Running 1. Check that all tubing and wiring are properly connected. 2. Check that the gas and liquid side service valves are fully open. Prepare remote controller 1 Open the bottom of remote control with turning it clockwise. 2 Insert the battery. (Match the metal terminals between remote control and battery.) 3 Align the lines with each other, close the bottom of the remote control with turning it counterclockwise.
5RMI0-02A Installation Pump Down This is performed when the unit is relocated or the refrigerant circuit is serviced. Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant. CAUTION Be sure to perform Pump Down procedure in the cooling mode. Pump Down Procedure 1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve. 2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant. 3.
Installation 5RMI0-02A Installation guide at the seaside CAUTION 1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. 3.
5RMI0-02A Installation 13.2 AS-W2462EF0(P24EL) Installation Map Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealant) Bend the pipe as closely on the wall as possible, but be careful that it doesn't break. Vinyl tape (Wide) Saddle • Apply after carrying out a drainage test. • To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Installation 5RMI0-02A Select the best Location Indoor unit - There should not be any heat or steam near the unit. - Select a place where there are no obstacles around of the unit. - Make sure that condensation drainage can be conveniently routed away. - Do not install near a doorway. - Ensure that the interval between a wall and the left (or right) of the unit is more than 100mm. The unit should be installed as high as possible on the wall, allowing a minimum of 200mm from ceiling.
5RMI0-02A Installation Fixing Installation Plate The wall you select should be strong and solid enough to prevent vibration Installation Plate 1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts. - Mount the installation plate horizontally by aligning the centerline using Horizontal meter . 2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate.
Installation 5RMI0-02A Flaring Work Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure. Cut the pipes and the cable 1. Use the piping kit accessory or the pipes purchased locally. 2. Measure the distance between the indoor and the outdoor unit. 3. Cut the pipes a little longer than measured distance. 4. Cut the cable 1.5m longer than the pipe length. Copper pipe 90° Slanted Uneven Rough Burrs removal Pipe 1.
5RMI0-02A Installation Connecting the Piping Indoor unit 1. Open the panel of the indoor unit. 2. Remove the chassis cover from the unit by loosing 3 screws. Chassis cover 3. Pull back the tubing holder. 4. Remove the pipe port cover and position the piping. Indoor unit back side view Right Tubing holder Left Backwards Assembly of chassis cover Indoor unit 1. Insert 5 hooks of the chassis cover into the square hole of the chassis certainly. 2.
Installation 5RMI0-02A Good case • Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly. Bad case • Following bending case from right to left directly may cause damage to the tubing. CAUTION Installation Information. For right piping. Follow the instruction above.
5RMI0-02A Installation Installation of Indoor Unit 1. Hook the indoor unit onto the upper portion of the installation plate.( engage the three hooks at the top of the indoor unit with the upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it left and right Installation plate 2. Unlock the tubing holder from the chassis and mount between the chassis and installation plate in order to separate the bottom side of the indoor unit from the wall.
Installation 5RMI0-02A Connecting the installation pipe and drain hose to the indoor unit. 1. Align the center of the pipes and sufficiently tighten the flare nut by hand Indoor unit tubing Flare nut Pipes 2. Tighten the flare nut with a wrench Outside Diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Open-end wrench (fixed) Torque kgf·cm N·m 180~250 17.6~24.5 340~420 33.3~41.2 550~660 53.9~64.7 630~820 61.7~80.4 Flare nut Connection pipe Wrench Indoor unit tubing 3.
5RMI0-02A Installation Outdoor unit 1. Remove the tubing cover from the unit by loosening the screw. 1(L) 2(N) 1(L) 2(N) 3 Outdoor Unit Connecting cable Cover control 2. Align the center of the pipings and sufficiently tighten the flare nut by hand. 3. Finally, tighten the flare nut with torque wrench until the wrench clicks. - When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. Outside Diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.
Installation 5RMI0-02A Connecting the Cables m m 5m ± 45 Indoor Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.) GN 10 m ±3 /YL 20 mm (mm2) 1.
5RMI0-02A Installation 1(L) 2(N) 1(L) 2(N) 3 Outdoor Unit Connecting cable Cover control 6. Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. 7. Always install an earth leakage circuit breaker in a wet or moist area. 8. The following would be caused by voltage drop. - Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload.
Installation 5RMI0-02A Checking the Drainage To check the drainage. 1. Pour a glass of water on the evaporator. 2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. Connecting area drain hose Leakage checking *The feature can be changed according to type of model. Drain pan Drain hose Leakage checking Drain piping Downward slope 1. The drain hose should point downward for easy drain flow. 2.
5RMI0-02A Installation Installing drain piping of the outdoor unit Depending on installation site, it may be required to install drain plug for drainage (Supplied with the unit). In cold areas, do not use a drain hose with the outdoor unit. Otherwise, drain water may freeze, impairing the heating performance. In cases where the outdoor unit is installed below the indoor unit perform the following. 1. Tape the piping, drain hose and connecting cable from down to up. 2.
Installation 5RMI0-02A Air Purging The air and moisture remaining in the refrigerant system have undesirable effects as indicated below. 1. Pressure in the system rises. 2. Operating current rises. 3. Cooling(or heating) efficiency drops. 4. Moisture in the refrigerant circuit may freeze and block capillary tubing. 5. Water may lead to corrosion of parts in the refrigeration system. Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor unit.
5RMI0-02A Installation Soap water method 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valve. 3. Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. 4. If bubbles come out, the pipes have leakage Outdoor unit Gas side 3-way valve Liquid side 3-way or 2-way valve Evacuation Cap 1.
Installation 5RMI0-02A Test Running 1. Check that all tubing and wiring are properly connected. 2. Check that the gas and liquid side service valves are fully open. Prepare remote controller 1. Remove the battery cover by pulling it according to the arrow direction. 2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly. 3. Reattach the cover by pushing it back into position. NOTICE • Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
5RMI0-02A Installation Pump Down This is performed when the unit is relocated or the refrigerant circuit is serviced. Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant. CAUTION Be sure to perform Pump Down procedure in the cooling mode. Pump Down Procedure 1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve. 2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant. 3.
Installation 5RMI0-02A Installation Guide for Areas Exposed to Sea Wind CAUTION 1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. 3.
5RMI0-02A Installation 13.3 AS-W126MMS3(H12AK) Installation Map Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealant) Bend the pipe as closely on the wall as possible, but be careful that it doesn't break. Vinyl tape (Wide) Saddle • Apply after carrying out a drainage test. • To carry out the drainage test, remove the air filters and pour water into the heat exchanger.
Installation 5RMI0-02A Select the best Location Indoor unit - There should not be any heat or steam near the unit. - Select a place where there are no obstacles around of the unit. - Make sure that condensation drainage can be conveniently routed away. - Do not install near a doorway. - Ensure that the interval between a wall and the left (or right) of the unit is more than 100mm. The unit should be installed as high as possible on the wall, allowing a minimum of 200mm from ceiling.
5RMI0-02A Installation Fixing Installation Plate The wall you select should be strong and solid enough to prevent vibration. 1. Before installation, confirm the position of a screw between chassis and Installation plate. 2. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts. - Mount the installation plate horizontally by aligning the centerline using Horizontal meter . A-Type B-Type 3. Measure the wall and mark the centerline.
Installation 5RMI0-02A Flaring Work Main cause for gas leakage is due to defect of flaring work. Carry out correct flaring work in the following procedure. Cut the pipes and the cable 1. Use the piping kit accessory or the pipes purchased locally. 2. Measure the distance between the indoor and the outdoor unit. 3. Cut the pipes a little longer than measured distance. 4. Cut the cable 1.5m longer than the pipe length. Copper pipe 90° Slanted Uneven Rough Burrs removal Pipe 1.
5RMI0-02A Installation Connecting the Piping Indoor unit 1. Open the panel of the indoor unit. 2. Remove the chassis cover from the unit by loosing 3 screws. Chassis cover 3. Pull back the tubing holder. 4. Remove the pipe port cover and position the piping. Indoor unit back side view Right Downwards Tubing holder Left Backwards Good case • Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side slowly.
Installation 5RMI0-02A Installation of Indoor Unit 1. Hook the indoor unit onto the upper portion of the installation plate.( engage the three hooks at the top of the indoor unit with the upper edge of the installation plate) Ensure that the hooks are properly seated on the installation plate by moving it left and right Installation plate 2. Unlock the tubing holder from the chassis and mount between the chassis and installation plate in order to separate the bottom side of the indoor unit from the wall.
5RMI0-02A Installation Connecting the installation pipe and drain hose to the indoor unit. 1. Align the center of the pipes and sufficiently tighten the flare nut by hand Indoor unit tubing Flare nut Pipes 2. Tighten the flare nut with a wrench Outside Diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Open-end wrench (fixed) Torque kgf·cm N·m 180~250 17.6~24.5 340~420 33.3~41.2 550~660 53.9~64.7 630~820 61.7~80.4 Flare nut Connection pipe Wrench Indoor unit tubing 3.
Installation 5RMI0-02A Outdoor unit 1. Remove the tubing cover from the unit by loosening the screw. Tubing cover 2. Align the center of the pipings and sufficiently tighten the flare nut by hand. 3. Finally, tighten the flare nut with torque wrench until the wrench clicks. - When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. Outside Diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.
5RMI0-02A Installation Connecting the Cables mm ±3 10 Indoor Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No. are the same as those of the indoor unit.) GN /Y L 20 mm (mm2) 1. Insert the connecting cable through the bottom side of indoor unit and connect the cable. 2.
Installation 5RMI0-02A 6. Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. 7. Always install an earth leakage circuit breaker in a wet or moist area. 8. The following would be caused by voltage drop. - Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload. 9.
5RMI0-02A Installation Checking the Drainage To check the drainage. 1. Pour a glass of water on the evaporator. 2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit. Connecting area drain hose Leakage checking *The feature can be changed according to type of model. Drain pan Drain hose Leakage checking Drain piping Downward slope 1. The drain hose should point downward for easy drain flow. 2.
Installation 5RMI0-02A In cases where the outdoor unit is installed below the indoor unit perform the following. Forming the Piping Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tapes. - If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately. 1. Tape the piping, drain hose and connecting cable from down to up. 2.
5RMI0-02A Installation Air Purging The air and moisture remaining in the refrigerant system have undesirable effects as indicated below. 1. Pressure in the system rises. 2. Operating current rises. 3. Cooling(or heating) efficiency drops. 4. Moisture in the refrigerant circuit may freeze and block capillary tubing. 5. Water may lead to corrosion of parts in the refrigeration system. Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor unit.
Installation 5RMI0-02A Soap water method 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valve. 3. Apply a soap water or a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. 4. If bubbles come out, the pipes have leakage Liquid side 2-way valve (Close) Gas side Evacuation Cap 1.
5RMI0-02A Installation Test Running 1. Check that all tubing and wiring are properly connected. 2. Check that the gas and liquid side service valves are fully open. Prepare remote controller 1. Remove the battery cover by pulling it according to the arrow direction. 2. Insert new batteries making sure that the (+) and (–) of battery are installed correctly. 3. Reattach the cover by pushing it back into position. NOTICE • Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
Installation 5RMI0-02A Pump Down This is performed when the unit is relocated or the refrigerant circuit is serviced. Pump Down means collecting all refrigerant into the outdoor unit without the loss of refrigerant. CAUTION Be sure to perform Pump Down procedure in the cooling mode. Pump Down Procedure 1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve. 2. Open the gas side service valve halfway and purge the air in the manifold hose using the refrigerant. 3.
5RMI0-02A Installation Installation Guide for Areas Exposed to Sea Wind CAUTION 1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced. 2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance. 3.
value unit x,x kW heating / Warmer SCOP/W x,x SCOP/C x,x - Inverter Single kW kW kW kW 2.4 - x,x x,x x,x x,x x,x kW kW kW kW kW Tj=operating limit COPd COPd COPd COPd COPd x,x x,x x,x x,x x,x - - Pdh 2.5 3.8 4.6 5.5 2.5 2.4 Tj=operating limit COPd COPd COPd COPd COPd COPd Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature Tj=-7ºC Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature Tj=operating limit Pdh Pdh Pdh Pdh kW kW kW kW kW kW - Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 1.
Indoor unit Pdesignh Pdesignh heating / Colder x,x kW heating / Warmer SCOP/W x,x - Inverter Single - x,x x,x x,x x,x x,x kW kW kW kW kW Tj=operating limit COPd COPd COPd COPd COPd x,x x,x x,x x,x x,x - - Pdh 2.4 3.7 4.9 5.8 2.4 2.
Pdesignh heating / Colder x,x x,x kW kW kW kW heating / Warmer heating / Colder SCOP/C x,x SCOP/W x,x SEER 9.1 SCOP/A 5.2 symbol value - - - unit 2.5 1.8 1.2 1.0 kW kW kW kW Inverter Single x,x kW Tj=operating limit COPd x,x x,x x,x x,x x,x - - Pdh COPd COPd COPd COPd Tj=operating limit kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature x,x x,x x,x x,x Pdh Pdh Pdh Pdh kW kW kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 3.1 1.7 1.2 0.9 3.4 3.
x,x x,x kW kW kW kW heating / Warmer heating / Colder SCOP/C x,x SCOP/W x,x - - SEER 8.9 SCOP/A 5.1 - symbol value unit 1.5 1.1 3.5 2.6 kW kW kW kW Inverter Single 3.5 x,x kW Tj=operating limit COPd x,x x,x x,x x,x x,x - - Pdh COPd COPd COPd COPd Tj=operating limit kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature x,x x,x x,x x,x Pdh Pdh Pdh Pdh kW kW kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 2.0 1.4 0.9 3.7 3.
Pdesignh heating / Colder x,x x,x kW kW kW kW heating / Colder heating / Warmer Seasonal efficiency cooling heating / Average Item SCOP/C x,x SCOP/W x,x SEER 6.2 SCOP/A 4.0 - - - symbol value unit 2.5 1.7 1.2 0.
Pdesignh heating / Colder x,x x,x kW kW kW kW heating / Colder heating / Warmer Seasonal efficiency cooling heating / Average Item SCOP/C x,x SCOP/W x,x SEER 6.1 SCOP/A 4.0 - - - symbol value unit 3.5 2.5 1.7 1.
Pdesignh heating / Colder x,x x,x kW kW kW kW heating / Warmer heating / Colder SCOP/C x,x SCOP/W x,x SEER 6.2 SCOP/A 3.8 - - - symbol value unit 1.3 1.2 2.5 1.8 kW kW kW kW Inverter Single x,x kW Tj=operating limit COPd x,x x,x x,x x,x x,x - - Pdh COPd COPd COPd COPd Tj=operating limit kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature x,x x,x x,x x,x Pdh Pdh Pdh Pdh kW kW kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 1.4 1.1 1.3 2.8 2.8 2.
Pdesignh heating / Colder x,x x,x kW kW kW kW heating / Warmer heating / Colder SCOP/C x,x SCOP/W x,x SEER 6.1 SCOP/A 3.8 - - - symbol value unit 1.6 1.2 3.5 2.6 kW kW kW kW Inverter Single x,x kW Tj=operating limit COPd x,x x,x x,x x,x x,x - - Pdh COPd COPd COPd COPd Tj=operating limit kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature x,x x,x x,x x,x Pdh Pdh Pdh Pdh kW kW kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 1.7 1.2 1.3 3.4 3.2 2.
Pdesignh heating / Colder x,x x,x kW kW kW kW heating / Warmer heating / Colder SCOP/C x,x SCOP/W x,x SEER 6.1 SCOP/A 3.8 - - - symbol value unit 2.4 1.1 5.2 3.7 kW kW kW kW Inverter Single x,x kW Tj=operating limit COPd x,x x,x x,x x,x x,x - - Pdh COPd COPd COPd COPd Tj=operating limit kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature x,x x,x x,x x,x Pdh Pdh Pdh Pdh kW kW kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 2.8 1.8 1.1 4.7 4.7 4.
Pdesignh heating / Colder x,x x,x kW kW kW kW heating / Warmer heating / Colder SCOP/C x,x SCOP/W x,x SEER 5.9 SCOP/A 3.8 - - - symbol value unit 1.3 1.2 2.5 1.8 kW kW kW kW Inverter Single x,x kW Tj=operating limit COPd x,x x,x x,x x,x x,x - - Pdh COPd COPd COPd COPd Tj=operating limit kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature x,x x,x x,x x,x Pdh Pdh Pdh Pdh kW kW kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 1.4 1.1 1.3 2.8 3.0 2.
Pdesignh heating / Colder x,x x,x kW kW kW kW heating / Warmer heating / Colder SCOP/C x,x SCOP/W x,x SEER 5.8 SCOP/A 3.8 - - - symbol value unit 1.6 1.2 3.5 2.6 kW kW kW kW Inverter Single x,x kW Tj=operating limit COPd x,x x,x x,x x,x x,x - - Pdh COPd COPd COPd COPd Tj=operating limit kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature x,x x,x x,x x,x Pdh Pdh Pdh Pdh kW kW kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 1.7 1.1 1.2 3.2 3.1 2.
Pdesignh heating / Colder x,x x,x 1.3 1.3 3.5 1.8 Inverter Single heating / Warmer heating / Colder SCOP/C x,x SCOP/W x,x SEER 4.3 SCOP/A 4.1 - - - unit x,x kW Tj=operating limit COPd x,x x,x x,x x,x x,x - - Pdh COPd COPd COPd COPd Tj=operating limit kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature x,x x,x x,x x,x Pdh Pdh Pdh Pdh kW kW kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 1.5 1.2 1.3 2.7 3.0 2.
Pdesignc Pdesignh Pdesignh Pdesignh Design load cooling heating / Average heating / Warmer heating / Colder x,x kW heating / Warmer SCOP/W x,x - Inverter Single 1.6 1.3 3.5 2.6 kW kW kW kW 3.2 - x,x x,x x,x x,x x,x kW kW kW kW kW Tj=operating limit COPd COPd COPd COPd COPd x,x x,x x,x x,x x,x - - Pdh 2.5 4.0 5.0 6.3 2.6 2.
symbol Pdesignc Pdesignh Pdesignh Pdesignh Item Design load cooling heating / Average heating / Warmer heating / Colder x,x x,x 5.0 4.1 kW kW kW kW Pdc Pdc Pdc Pdc 5.0 3.7 2.4 1.1 kW kW kW kW Inverter Single 3.1 5.0 7.4 9.
Pdesignh x,x x,x kW kW kW kW heating / Warmer heating / Colder SCOP/C x,x SCOP/W x,x SEER 6.1 SCOP/A 3.8 - - - symbol value unit 6.8 5.0 3.2 1.4 kW kW kW kW Inverter Single x,x kW Tj=operating limit COPd x,x x,x x,x x,x x,x - - Pdh COPd COPd COPd COPd Tj=operating limit kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature x,x x,x x,x x,x Pdh Pdh Pdh Pdh kW kW kW kW kW kW Tj=2ºC Tj=7ºC Tj=12ºC Tj=bivalent temperature 3.3 2.1 0.9 6.2 5.5 5.
5RMI0-02A Energy label 15. Energy label • Labelling Efficiency Energy Efficiency Class A+++ A++ A+ A B C D E F G Split and Window systems SEER SCOP SEER≥8.5 SCOP≥5.1 6.1 ≤ SEER < 8.5 4.6 ≤ SCOP < 5.1 5.6 ≤ SEER < 6.1 4.0 ≤ SCOP < 4.6 5.1 ≤ SEER < 5.6 3.4 ≤ SCOP < 4.0 4.6 ≤ SEER < 5.1 3.1 ≤ SCOP < 3.4 4.1 ≤ SEER < 4.6 2.8 ≤ SCOP < 3.1 3.6 ≤ SEER < 4.1 2.5 ≤ SCOP < 2.8 3.1 ≤ SEER < 3.6 2.2 ≤ SCOP < 2.5 2.6 ≤ SEER < 3.1 1.9 ≤ SCOP < 2.2 SEER < 2.6 SCOP < 1.
Energy label 164 5RMI0-02A AS-W096MMS3(H09AK) AS-W126MMS3(H12AK) AS-W096BNR3(D09AK) AS-W126BNR3(D12AK) Inverter Single
5RMI0-02A Energy label AS-W096BWR4(A09WL) AS-W096BRR4(A09RL) US-W096B8F0(P09RL) AS-W126BWR4(A09WL) AS-W126BRR4(A09RL) US-W126B8F0(P12RL) AS-W186CRR4(A18RL) US-W096H4A0(E09EL) US-W096HSA0(Z09SL) Inverter Single 165
Energy label 166 5RMI0-02A US-W126H4A0(E12EL) US-W126HSA0(Z12SL) AS-W096NRR0(A09LL) AS-W126NRR0(A12LL) AS-W1862WR0(D18RL) AS-W1862EF0(P18EL) Inverter Single
5RMI0-02A Energy label AS-W2462WR0(D24RL) AS-W2462EF0(P24EL) Test Condition Temp. condition Cooling Test Heating Test (Average) Heating Test (Warmer) Heating Test (Colder) Tdesign temp. Tdesignc 27(19)/35(24) Tdesignh 20(15)/ -10(-11) Tdesignh 20(15)/ 2(1) Tdesignh 20(15)/-22 (-23) A 27(19) / 35(24) 20(15) / -7(-8) N.A.
P/No.: MFL66305320 Air Conditioner 20 Yeouido-dong, Yeongdeungpo-gu, Yeouido P.O.Box 335 Seoul, 150-721, Korea. http://www.lgeaircon.com All rights reserved Printed in Korea February / 2014 The specifications, designs, and information in this brochure are subject to change without notice. The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system.