Datasheet
synchro (inverter)
UU48W / UU60W
DC inverter
Nominal Capacity Cooling kW
Capacity (UK) Cooling kW
Nominal Capacity (T1) Heating kW
Power Supply to Unit V/Phase/Hz
Power supply to
Inter connecting Cables
cores and rating No. Amps
Running Current Cooling Amps
Running Current Heating Amps
Power Input Cooling kW
Power Input Heating kW
Start Current Cooling Amps
Start Current Heating Amps
Circuit Breaker Amps
T1 EER Cool (W/W)
T1 COP Heat (W/W)
ECA compliant
Air Circulation
(High Speed)
Outdoor (m3/min)
Sound Levels
(High Speed)
Outdoor dB(A)+/-3 (at 1.0m)
Outdoor Units WxHxD (mm)
Outdoor Units (Kg)
Liquid (Inch)
Suction (Inch)
Maximum Elevation (m)
Max. Distance between In & Out (m)
Factory charge (Kg)
Charged for — m (m)
Additional g/m (g/m)
14.1
13.3
16.1
240/1/50
Outdoor
4*5A
26.6
27.3
4.9
5
43
43
50
2.9
2.9
n
90
59
806x1507x690
142
3/8
3/4
30
70
7.1
30
50
16.4
15.4
18.9
240/1/50
Outdoor
4*5A
31.3
35.5
5.8
6.6
74
74
63
2.8
2.4
n
90
59
806x1507x690
148
3/8
3/4
30
70
7.1
30
50
Specification
UU48W UYB UU60W UYB
Model Indoor Unit
Outdoor Unit
33
page
www.lgaircon.co.uk LG Air Conditioning synchro
synchro
Note: Due to our policy of innovation
some specifications may be changed
without notification.
T1 Condition: Cooling - indoor 27Cwb, 19Cdb; outdoor 35Cdb
Heating - indoor 20Cdb: outdoor 7Cdb, 6Cwb
UK Condition: Cooling - indoor 23Cdb, 16Cwb; outdoor 30Cdb
60724 LG Catalogue Spring07 23/3/07 10:14 am Page 33