Datasheet

fixed speed condensers
UU12 / UU18
UU24 / UU30
UU37 / UU48
UU60
Anti Corrosion Gold Fin • Natural Wind Operation
Wireless Remote Controller • Sleep Operation
Auto Changeover • Soft Dry Operation
24-Hour ON/OFF Setting Timer • Auto Restart
UU12 UU24/UU30UU18
UU37 UU48/UU60
Nominal Capacity Cooling kW
Capacity (UK) Cooling kW
Nominal Capacity (T1) Heating kW
Power Supply to Unit V/Phase/Hz
Power supply to
Inter connecting Cables
cores and rating No. Amps
Running Current Cooling Amps
Running Current Heating Amps
Power Input Cooling kW
Power Input Heating kW
Start Current Cooling Amps
Start Current Heating Amps
Circuit Breaker Amps
T1 EER Cool (W/W)
T1 COP Heat (W/W)
ECA compliant
Air Circulation Outdoor (m3/min)
Sound Levels Outdoor dB(A)+/-3 (at 1.0m)
Outdoor Units WxHxD (mm)
Outdoor Units (Kg)
Liquid (Inch)
Suction (Inch)
Drain (ID) (mm)
Maximum Elevation (m)
Max. Distance between In & Out (m)
Factory charge (Kg)
Charged for — m (m)
Additional g/m (g/m)
3.5
3.1
4
240/1/50
Outdoor
4*5A
6.5
6.6
1.3
1.4
24
24
16
2.7
2.9
n
26
47
770 x 540 x 245
31
1/4
3/8
32
10
15
1.2
7.5
20
5.3
4.7
5.8
240/1/50
Outdoor
4*5A
9
9.9
1.9
2.1
35
35
16
2.8
2.8
n
58
52
870 x 655 x 320
52
1/4
1/2
32
30
50
1.3
7.5
35
7
6.2
7.7
240/1/50
Outdoor
4*5A
12
13.1
2.5
2.8
62
62
20
2.8
2.8
n
58
52
870 x 808 x 320
60
1/4
1/2
32
30
50
1.95
7.5
35
8.8
7.8
9.7
240/1/50
Outdoor
4 *5A
19.2
19.5
4
4
35
35
32
2.2
2.4
n
53
53
870 x 808 x 320
64
1/4
5/8
32
30
50
2.1
7.5
35
10.6
9.3
11.6
415/3/50
Outdoor
4*5A
7.9
7.1
4.1
3.6
18
18
20
2.6
3.2
n
64
52
870 x 1060 x 320
80
1/4
5/8
32
30
50
2.6
7.5
40
14.1
12.4
15.5
415/3/50
Outdoor
4*5A
12.7
11.7
5.8
5.5
42
42
20
2.4
2.8
n
106
57
900 x 1165 x 370
105
3/8
3/4
32
30
50
4.2
30
70
15.8
14
17.4
415/3/50
Outdoor
4*5A
13.5
13.8
6.6
6.7
63
63
32
2.4
2.6
n
106
57
900 x 1165 x 370
93
3/8
3/4
32
30
50
4.7
30
80
Specification
UU12ULC UU18UEC UU24UEC UU30UEC UU37UEC UU48UHC UU60UHB
Model Indoor Unit
Outdoor Unit
29
page
www.lgaircon.co.uk LG Air Conditioning fixed speed condensers
fixed speed condensers
Note: Due to our policy of innovation
some specifications may be changed
without notification.
T1 Condition: Cooling - indoor 27Cwb, 19Cdb; outdoor 35Cdb
Heating - indoor 20Cdb: outdoor 7Cdb, 6Cwb
UK Condition: Cooling - indoor 23Cdb, 16Cwb; outdoor 30Cdb