Brochure
Outside Air Vents
Allows up to 50CFM of outside air into
Conditioned air space when opened.
1
Model LP073HDUC, EER 13.3, www.ahridirectory.org (April 2019)
2
Indoor sound pressure levels down to 45dB(A), comparable to a quiet urban nighttime
3
Power cords are available as a separate accessory
Heating Pump Models
Model
Unit LP073HDUC LP093HDUC1 LP123HDUC1 LP153HDUC
Power Supply V/Hz/O
208/60/1 230/60/1
208/60/1 230/60/1 208/60/1 230/60/1 208/60/1 230/60/1
Cooling Capacity Btu/h 7,100 7,300 10,000 10,200 11,900 12,100 14,900 15,100
Heating Capacity
Btu/h 6,200 6,400 8,600 8,800 10,300 10,500 13,200 13,400
Electric Heater
Capacity
with 15A Cord
3
Btu/h (kW) 7,800 (2.3) 8,100 (2.4) 7800 (2.3) 8100 (2.4) 7800 (2.3) 8100 (2.4) 7800 (2.3) 8100 (2.4)
with 20A Cord
3
Btu/h (kW)
10,900 (3.2) 11,200 (3.3) 10900 (3.2) 11200 (3.3) 10900 (3.2) 11200 (3.3) 10900 (3.2) 11200 (3.3)
with 30A Cord
3
Btu/h (kW)
15,700 (4.6) 16,000 (4.7)
15700 (4.6) 16000 (4.7) 15700 (4.6) 16000 (4.7) 15700 (4.6) 16000 (4.7)
EER
13.3
12.4 11.9 11.2
COP
3.6
3.5 3.5 3.1
MCA
with 15 A Cord
3
A 14.5 13.6 14.5 13.6 14.5 13.6 14.5 13.6
with 20A Cord
3
A
19.8 18.6 19.8 18.6 19.8 18.6 19.8 18.6
with 30A Cord
3
A
28.3 26.2 28.3 26.2 28.3 26.2 28.3 26.2
MOP
with 15A Cord
3
A
15 15 15 15
with 20A Cord
3
A
20 20 20 20
with 30A Cord
3
A
30 30 30 30
Weight (Net/Shipping)
lbs.
95/108 104/117 104/117 115/128
Dimensions (W x H x D)
in.
42 x 16 x 19-7/8 42 x 16 x 19-7/8 42 x 16 x 19-7/8 42 x 16 x 19-7/8
Sound Pressure Max (IDU/ODU)
dB(A)
45/61 46/61 50/63 51/64
Indoor Air Circulation Max
CFM
270 270 420 420
Dehumidification
pts/hr
1.7 2.6 3.0 4.3
Cooling Rated Amps
A
2.7 2.5 4.0 3.7 5.1 4.7 6.6 6.1
Heating Rated Amps
A
2.6 2.4 3.5 3.2 4.4 4.1 6.2 5.7
Cooling Power Input
W
535 550 800 820 1000 1020 1330 1345
Heating Power Input
W
500 520 720 735 865 880 1250 1265
|
Freeze Room Protection
Electronic temperature controls constantly
monitor and maintain indoor temperature
to prevent freezing.
Emergency Heat
(Heat Pump Models Only)
Separate Indoor & Outdoor BLDC Motors
Dual motor conguration allows the lowest
sound rating in the industry while also providing
the highest level of energy efciency.
Defrost Control
(Heat Pump Models Only)
Shuts down the indoor fan to prevent cold air
from being blown into the room. Also removes
frost from outdoor coil when the outdoor
temperature is low.
Sensors
Four sensors provide highly efcient
operation and maximizes guest comfort.
Pressure Control
Protects guests by shutting down the
compressor in abnormally high pressure conditions.
High Efciency Compressor
Energy efcient LG compressor.
Power Cord
Choose from three options based on
your requirements (208/230V only).
Dip Switch setting
Saves money by control of the lowest and highest temperature.