Installation guide

14 Indoor Unit
• Drain piping must have down-slope (1/50 to 1/100): be sure not to
provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra force
on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is
32 mm(1-1/4 inch).
Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe inner
diometes Ø 25 mm(1 inch) and pipe fittings
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Connect the main drain pipe to the exterior
and leave it provisionally until the test comes
to an end.
Feed water to the flexible drain hose and
check the piping for leakage.
Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
When the test is complete, connect the flexi-
ble drain hose to the drain port on the indoor
unit.
Heat insulation material: Polyethylene foam with thick-
ness more than 8 mm(5/16 inch).
Drain test
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
Flexible drain hose
• TQ/TR: 700 mm
(27-9/16 inch)
• TM/TN/TP: 800 mm
(31-1/2 inch)
MAX
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Flexible drain hose
1/50~1/100
Flexible drain hoseFlexible drain hoseFlexible drain hose
• TQ/TR: 700 mm
(27-9/16 inch)
• TM/TN/TP: 800 mm
(31-1/2 inch)
MAX
Drain Piping
CAUTION : The supplied flexible drain
hose should not be curved, neither
screwed. The curved or screwed hose
may cause a leakage of water.
Installation