User manual

AC Manager
3-73
Pattern management
A button to manage the pattern for device connected control.
Device connected control setting
Current setting pattern is reflected to device connected setting list.
Save
Saves current setting.
1
2
3
3. AC Manager Operation
Device connected control
Emergency Stop Interlocking, the device connected control, is a function that stops all indoor units and
ventilation units in case of fire and other emergency. The summary on this function is as follows.
- Save current setting status function
The indoor units and ventilation units being currently monitored is data-based and saved.
- Operation setting function
If you set the external device and product status in the operation setting, the setting operation shall
be carried out when the device recognizes DI signal.
- Emergency stop function
When external signal is detected, this function is used to save current setting status and stop the
operation of all indoor device and ventilation product. Once the external signal is recognized, the
operation status of the product isnt recovered even if the external signal doesnt last.
Below is the main screen of device connected control.
Below is the description on each menu on above screen.
2
1
3