Instructions / Assembly
The wall sleeve must be installed before the air conditioner or heat pump chassis can be set in 
place. Read the instructions thoroughly before proceeding. 
When  230/208  volt  PTAC  units  are  to  be  installed, 
the  power  supply  may  be  either  cord  connected  or 
permanent  wiring.    Permanent  wiring  may  be  done 
through  the hardwire  junction box, or the accessory 
subbase. 
When  265  volt  PTAC  units  are  to  be  installed,  the 
power supply must be permanent wiring. Permanent 
wiring may be done through the accessory hardwire 
junction box, or the accessory subbase.  An exposed 
cord connection on 265 volt units are not permitted. 
The subbase accessory includes leveling legs. If ad-
ditional wall sleeve support is required and the sub-
base is not to be used an  accessory leveling leg kit 
may be installed. 
PRE-INSTALLATION CONSIDERATIONS 
The wall opening must be 16 ¼” x 42 ¼”. See Figure 2 
The wall sleeve must be located between 3 ¼” to 5 ½” above the floor (including carpeting). 
If the sleeve projects more than 4” into a room, install a subbase for support. 
If installed in a concrete or masonry wall, a lintel must be provided in the wall opening for support. Do not 
use the wall sleeve as a lintel. 
The wall sleeve must be horizontally level from side to side and 1/4” bubble tilt to the outside. 
The installer must determine and supply the mounting bolts and/or screws to attach the wall sleeve to the 
wall opening. 
The installer must provide adequate sealing and insulation around the sleeve after installation. 
If used, a 208/230-volt wall receptacle must be located within 28” of the lower right sleeve corner.  Do not 
use extension cords. 
If the wall is deeper than 13 7/8”, see your Sales Representative for correct installation. 
There should be nothing within 20” of the back that would interfere with heat radiation and exhaust air 
flow. 
Do not drill into bottom of sleeve wall unless installing internal Drain Kit refer to instructions. 
The wall sleeve must extend 5/8” beyond the building exterior to assure proper drainage and to allow 
weather-tight caulking. 
Made in USA 
Wall receptacle within 28” from bottom right side 
corner on 208/230 VAC only. 
FIGURE 1 
IMPORTANT: Installer is responsible for com-
plying with all building and National Electrical 
Codes. 
Wall Sleeve Installation Instructions 
1 