Cut Sheet
G-7088x/E4-cds
Product
Specifications
Z-MAX Digital
Switches
.........................
Leviton Mfg. Co., Inc.
P.O. Box 2210 • Tualatin, Oregon 97062 • Phone: (503) 404-5500 • Fax: (503) 404-5600
Visit our Website at: www.leviton.com
2
©2004 Leviton Mfg. Co.; Inc. • Specifications subject to change without notice.
CATALOG NUMBER GUIDE
Wallplate Ordering Guide:
Z-MAX Digital Switches fit a standard Decora opening, and can be
used with the following standard Leviton wallplate series:
803xx Decora Plus Screwless wallplates
804xx Decora plastic and metal wallplates - Standard Size
804xx-Nxx Decora nylon wallplate - Standard Size
PJ26x Decora nylon wallplates - Midway size
806xx Decora plastic wallplate - Midway Size
S026x Oversized metal wallplate
Browse the Leviton website for more wallplate options
LUMA-NET® III
• Must be daisy chained, station to station.
• For Star configurations use a Luma-Net hub, LHUB8-000.
• Must be less than 2000 feet (600m)
• Must be run separately from line (mains) voltage
• The cable should not pass near any source of electrical noise such as
fluorescent circuits or motor wiring. Avoid close proximity to any AC
wiring. All control/power wiring must be in conduit.
LUMA-NET WIRE RECOMMENDATION:
• Two separate wire runs are required for Luma-Net - Communications
and Power
• Use RS485 compatible cable for the communications. We strongly
recommend the use of Belden 1502R or 1502P. This cable type
includes (2) #18 AWG wires in the same jacket for power runs.
REM+
REM -
COM
TERM
LOCK
+V
1
2
3
4
5
6
U
p
to
1
#
12
A
W
G
2#12AWG
2
#
1
2
AW
G
U
p
to
1
#
1
2
A
W
G
Drain/Shield - Insulated and tied together
(Ground at one point only-
probably an end)
Red
(+V )
Black (Common)
5
6
1
2
3
4
Phoenix/Luma-Net
Connector
Install termination jumper
if last station on a run
Entry Station
Luma-Net Hub
Entry Station
Note: Relay cabinet can be in the
middle of a daisy chain
For runs longer than 1,000 ft, we recommend pulling
an extra pair of #12 AWG wire for power runs.
G-7088 Z-MAX Dig.Switches 8/10/04 11:39 AM Page 2
• Capacitance of wire shall be 15pF/ft. or less
• Nominal Impedance of wire shall be between 100-120 ohms
• Drain/Shields to be tied together, insulated and grounded
(on one end only)
• At the last control station or dimmer cabinet on both ends of the run, a
small jumper wire must be run between two terminals on the connec-
tor. This jumper wire properly terminates the digital communications
lines at the end of the line.
• Belden 9829
• Belden 9729
• Belden 8102
• The following cable types are also acceptable. These cables
include (2) Twisted Pair, #24 AWG, stranded conductors. The
spare pair is for future uses. Note that these cable types require
a separate pair of stranded wires for power, minimum #18 AWG.