Instructions / Assembly

RESIDENTIAL PANEL SURGE PROTECTIVE DEVICE (SPD)
Cat No. 51110
DI-R02-51110-21A
INSTALLATION
ENGLISH
WARNINGS AND CAUTIONS:
THIS
DEVICE
MUST BE
INSTALLED
BY AN
ELECTRICIAN.
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT THE POWER IS OFF BEFORE WIRING OR SERVICING!
TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH ELECTRICAL CODES AND REGULATIONS.
INSTALL THIS DEVICE ONLY ON A SINGLE BRANCH CIRCUIT PROTECTED BY A FUSE OR A CIRCUIT BREAKER.
USE THIS DEVICE ONLY WITH COPPER OR COPPER CLAD WIRE.
TO MAINTAIN ENVIRONMENTAL RATING, IT IS THE RESPONSIBILITY OF THE ELECTRICIAN TO ATTACH THIS DEVICE USING APPROVED METHODS FOR THE INTENDED APPLICATION.
DESCRIPTION:
Leviton’s
511
10-SRG
Residential
Panel
Surge
Protection
Device
(SPD)
is
a
high-performance
T
ransient
V
oltage
Surge
Suppressor
.
The
Residential
Panel
SPD
unit
is
designed
for
use
on
240/120
V
AC
at
the home's breaker
panel.
Diagnostics
provide visual
indicators
for monitoring the
240/120
VAC
protection
status.
TO INSTALL:
1.
RESTORE
POWER,
if
necessary
.
2. Verify that the electrical
system
in use is
240/120
VAC single
phase
by the safe and proper use of AC Voltage
Measurement Equipment.
3. TURN OFF
POWER.
4.
Identify
the
device
or
load
to
be
protected.
Locate
the SPD
unit
as
close
as
possible
to
the
electrical
panel
serving
the loads
to
be
protected,
to
minimize
the
ef
fects
of
connection
lead-length
resistance
and
inductance.
W
ARNING:
Matching
the SPD
model
and
electrical
system
line
voltage
is
critical!
Identify
the
system
to
be
protected
by
measuring
L-N
and
L-L
voltages.
Use
extreme
caution
while
making
voltage
measurements!
Confirm that the maximum
measured
voltage
does
not
exceed
the maximum
continuous
line voltage
specified
for the
51110-SRG
unit to be installed or
damage
will
occur. Figure 1 illustrates the wiring
connection
for the 511
10-
SRG.
5.
Leads
shall be 12 AWG 18"
maximum. Leads
from the SPD must be
connected
to the power mains through a 20 Amp (maximum)
disconnect
and
fusing
means.
Either
dedicated branch
circuit
breakers
(independent single-pole preferred),
or a fused
disconnect
switch may be
used.
When the
SPD device
shares
a 2-pole
ganged breaker,
National Electric Code (NEC) and local
requirements
shall
prevail.
NOTE:
Sharing
of
breakers
is not
permitted
by CEC in
Canada.
NOTE: For best
performance,
installation wires should be twisted or bound
together
and
as
short
as possible.
Leads
from
the SPD
should
be
bundled
together
and
secured
with
cable ties
when
possible.
Conduit
shall
be
used
where
required
by
code.
For
best
suppression,
the cable
and
some
cable ties
may
be
cut
down from the
supplied
length to allow for a
shorter
installation
path.
6. Mount the SPD unit
securely.
The
51110-SRG
unit can be
surface mounted
by removing the cover, inserting
screws
through the two holes
provided,
tightening them to
secure
the unit, then
replacing
the
cover. The SPD unit can also be flush
mounted
by mounting the unit to a depth of 1 5/8
inches
[4.1 cm] (maximum), then, when the cover is
replaced,
it should be flush with the outer wall.
Direct
panel mounting
applications
should utilize a 7/8" (2.2
cm) conduit knockout hole with the
threaded
nipple
(provided).
7.
The
wires
should
be
routed
to
the
circuit
breaker
terminals
(refer
to
Figure
1)
using
the
shortest
path
(cutting
excess
wire
length)
to
the
power
line.
If
conduit
is
used,
use
conduit
as
required
by
NEC
and
local
requirements.
Avoid
sharp bends.
Lead wire insulation should not be cut or
damaged.
8.
Connection:
Connect the
black
wire
(marked
“Line
1”)
to
one
line,
and
the
other
black
wire
(marked
“Line
2”)
to
the
other
line.
These
Black
wires
may
be
connected
to
either
L1
or
L2
without
regard
to
phase angle.
9. The white wire should be
connected
to the
system’s
Neutral
bus.
10. The
green
wire is
attached
internally to the
51110-SRG
unit’s ground. The
green
wire must be
grounded
to the electrical panel’s ground
bus.
11. Check that all
connections
are
correct,
tight, and
secure.
POWER ON:
1. Activate the
system
by turning power ON (closing any main and SPD circuit
breakers).
The
green
indicator lights should be ON.
If
indicator lights are not
ON, call technical support.
Figure 1
Electrical
Wiring
Diagram
Figure 1
Schéma
de
câblage électrique
Figura 1 Diagrama de Cableado Eléctrico
L
Black / Noir / Negro
CB
L
Black / Noir / Negro
CB
51110-SRG
N
White / Blanc / Blanco
G
Green / Vert / Verde
Suitable
for
use
on a circuit
capable
of
delivering
no more than 10000
RMS
symmetrical amperes,
240
volts maximum
when
protected
by a 20
amp
circuit
breaker rated 240
volts maximum.
The interupt rating of the
fuse
or
circuit
breaker shall not be
less
than the
available
fault
current.
Dispositif
convenant aux
circuits
capables
de
livrer
un courant
maximal
de
10000
ampères symétriques efficaces,
à 240 volts au plus
protégés
par un fusible
ou
un
disjoncteur
de 20 A ayant cette
tension nominale.
La
capacité
nominale
de
sectionnement
des fusibles ou des
disjoncteurs employés
ne
peut être inférieure
au
courant
de fuite
possible.
Compatible
para usar en un circuito capaz de repartir no más de 10000 amperios
simétricos
RMS, 240 voltios
máximo
cuando está
protegido
por un
interruptor
de
circuitos
de 20
amperios
de
capacidad
de 240 voltios
máximo.
El grado de interrupción
del
interruptor
de
circuitos
o fusible no debe ser menor que la falla de corriente.
For
T
echnical
Assistance
Call:
1-800-824-3005
(U.S.A.
Only)
www
.leviton.com

Summary of content (2 pages)