Photocells
PHOTOCELL PLACEMENT
ODC0P/PCIND INDOOR PHOTOCELL MOUNTING LOCATION ATRIUM PHOTOCELL MOUNTING LOCATION
OUTDOOR PHOTOCELL MOUNTED IN 1/2” CONDUIT
Outdoor photocell mounted horizontally on roof or equal,
facing northern sky
Hooded portion on top, pointed away from any nighttime
light sources
Snow Line
North
SKYLIGHT APPLICATION WITH SKYLIGHT PHOTOCELL
Top of photocell should
be level with top of
skylight curb
Photocell in 1/2” conduit.
Photocell must be at
least 12” from side of
skylight and facing up
NOTE:
Support conduit from
unistrut as required
per NEC
UNISTRUT
JUNCTION BOX
1/4” ANGLE
SUPPORT
LOW VOLTAGE PHOTOCELL WITH OCCUPANCY
SENSOR ROOM CONTROL
NOTE: Power Pack and the load switched by the power pack MUST be fed from the same phase.
Blue
Black
Red
N
H
LOAD
Blue
Blue
White
Black
LOAD
Gray
Orange
Black
Red
OPP20-RD3
ODC0P-D0W
Low Voltage Photocell
Occupancy Sensor
Blue
Black
Red
Gray 1-10V Common
Gray 1-10V Common
Violet 1-10V Dim Out
Violet 1-10V Dim Out
ODC0P,
PCIND or
PCCxx
6-8 FT.
REFLECTING WALL USING INDOOR SENSOR
Light well - no sconces - indoor photocell
18”
PCIND
PCIND, PCCxx
Light well - with sconces - (UP or UP/DOWN)
Mount photocell in elevation on centerline
of fixture. Do not mount directly in line
with sconces.
Sconces
60
PCATR
Ideal photocell location is in the
middle of the atrium glass pointing
toward the glass