Specification

PRODUCT DATA
Photocells
FEATURES
Indoor photocells designed with a flat Fresnel lens looks
downward in a 60° cone of reference to measure actual
light on the work surface and reduce the influence of
stray light striking the photocell from nearby windows or
incidental side lighting
• Outdoor photocells are IP54 rated to guarantee ultimate
protection from dirt, dust, oil and other non-corrosive
material
• Measures light from any source in the visible spectrum
within a 60º cone or 180º angle of response depending on
the model
ODC0P-00W photocell with 60° clear lens operates
between 1-1,600FC. ODC0P should be surface mounted or
direct to ceiling box
ODC0P-S0W switching photocell with 60° clear lens
operates between 1-1,600FC. ODC0P should be surface
mounted or direct to ceiling box
ODC0P-D0W dimming photocell with 60° clear lens
operates between 1-1,600FC. ODC0P should be surface
mounted or direct to ceiling box
PCCxD-00W, PCCxS-00W, PCCSD-00W line voltage
photocells with 60° clear lens for applications where zone
control switching, dimming, and demand response are
required. Operates between 1-1,600FC. PCC photocells
should be mounted to the ceiling in standard 4”x4” square
or octagon electrical boxes
PCIND-000 indoor photocell with 60° clear Fresnel lens
is default setting = 75-800FC sensing range; can be field
adjusted to 800FC max sensing range.
PCIND should be
mounted
to the ceiling, facing down
PCIND-0SV side view photocell for applications where
ceiling mounting is required yet the view should be of
the lighting entering the space through a window; or, for
installation to the wall of skylights where the view should
be up into the skylight. Default setting = 0-30FC sensing
range; can be field configured with a jumper for a 3FC,
30FC, 300FC, or 600FC max sensing range
PCOUT-000 outdoor photocell is enclosed in a
weatherproof housing with a visor for shading and lens
protection. Default setting = 50-750FC sensing range
PCOUT-0SV side view photocell for applications where
wall mounting is required yet the view should be of the
lighting entering the space through a top/side and/or
face of the photocell. Reference placement diagrams.
Default setting = 0-30FC sensing range; can be field
configured with a jumper for a 3FC, 30FC, 300FC, or 600FC
max sensing range
PCATR-000 atrium photocell with opaque dome lens
filters 33% of light level in upper atrium. Default setting
= 215-2,690FC sensing range; can be field adjusted to
2,690FC max sensing range
PCSKY-000 skylight photocell with dark dome lens
filters 90% of light level in skylight. Default setting =
1,076-8,072FC sensing range; can be field adjusted to
8,072FC max sensing range
Diameter: 2.51”
0.76”
0.99”
0.23”
PHOTOCELL
(ODC0P)
PHOTOCELL
(PCCxD, PCCxS, PCCSD)
1.09”
1.16”
0.94”
2.39”
4.81”
ATRIUM/SKYLIGHT
(PCATR/PCSKY)
OUTDOOR
(PCOUT)
1.35”
1.85”
INDOOR
(PCIND)
1.15”
1.28”
SIDE VIEW PHOTOCELL
(PCIND-0SV/PCOUT-0SV)
Diameter: 2.04”
1.36”
1.28”
2.25”
DIMENSIONS