Installation Guide
OPERATION
PUSH-BUTTON:Cat.No.OSSNL/OSSNL-INx/OSS10-IDxhasa
push-button switch that toggles the lights (refer to gure).Ifthe
lightsareOFF,thelightswillturnONwhenthebuttonispressed,and
remainONinthepresenceofmotion.Intheabsenceofmotion,the
SensorUnitwilltime-outandturnthelightsOFF.
IfthelightsareON,thelightswillturnOFFwhenthebuttonispressed.
ThelightswillstayOFFregardlessofmotiondetected,untilthetime-
outexpires.Afterthetime-outexpires,thelightswillturnON(Auto-ON
Modeonly)withthenextdetectedmotion.Thisisusefulforslideor
lmpresentations.
NOTES:
• TheMotionIndicatorLEDwillblinkevery2secondswhilemotionis
detected.
• InManual-ONmode,thebuttonmustbepressedtoturnthe
lightsON.
PRODUCT INFORMATION
• Fortechnicalassistancecontactusat1-800-824-3005
• Visitourwebsiteatwww.leviton.com
PK-93369-10-00-0B
Field-of-View (Horizontal)
20 ft (6.1 m)
small motion
30 ft (9.1 m)
20 ft (6.1 m)
small motion
40 ft
(12.2 m)
Side (Vertical) Field-of-View
27 ft.
(8.2 m)
38 ft.
(11.7 m)
4 ft.
(1.2 m)
4.5 ft.
(1.4 m)
1
0
8.3
0
Sensor Unit
• Securedevicebyrmlytighteningmountingscrews.
• InstallDecora
®
stylewallplate(soldseparately).
Sensor and Wallplate Mounting:
Step 7
Wall surface
Device mounting screw
(2 places)
Wallplate
Wallplate
mounting
screw
(2 places)
Sensor Features Diagram
Lens with
PIR and LED
NightLight
Blinders
Control Panel
Cover
Push Button
LED
Indicator
Step 6 cont’d
Testing your Sensor prior to
completely mounting in wall box:
FEATURES AND SETTINGS:
TIME-DELAY:Cat.No.OSSNL/OSSNL-INx/OSS10-IDxwillturn
lightsONwhenmotionisdetected.Whenmotionisnolonger
detected,theSensorUnitwillwaitacertainamountoftimeand
thenturnthelightsOFF.Thiswaittimeiscalled‘time-out’.
The“time-out”isselectedfromfour(4)presetvalues.Pointingthe
arrowatoneofthemarkingsonthefacechoosesthevalueoftime.
ThebuttonLEDindicatorlightwillashtwicewhenthetimesetting
haschanged.Thefollowingselectionsareavailable:
OSSNL-IDx: Face Marking Value of Time
NOTE:The“time-out”isfactorypresettothirty(30)minutes
(refer to Sensor Features Diagram).
NOTE: All time durations mentioned in the instructions are
approximatewithin10seconds.
OSS10-IDx: Face Marking Value of Time
NOTE: The“time-out”isfactorypresettoten(10)minutes
(refer to Sensor Features Diagram).
NOTE: All time durations mentioned in the instructions are
approximatewithin10seconds.
RANGE:Todecreasedetectionrangeandsensitivity,rotatethe
knobcounter-clockwise(refer to Sensor Features Diagram).The
detectionsrangecanbeadjustedfrom100%downto35%.
MANUAL-ON MODE (OSSNL-INx ONLY):Thefactorydefault
settingfortheOSSNLisManual-ON.Tochangethissettingto
Auto-ON/OFF,turnthedialmarked“ONMODE/NLDIM”clockwise
anywhereintotheareathatindicates“AUTO”.Toreturnto
Manual-ON,turnthedialcounter-clockwiseanywhereintothearea
thatindicates“MAN”.
NOTE:OSS10isaManual-ONsettingonly.
NIGHTLIGHT:TheOSSNL/OSSNL-INx/OSS10-IDxrespondsto
theambientlightlevelpresentinaroom.TheOSSNL/OSSNL-INx/
OSS10-IDxusesaninternalphotocelltodetectwhentheambient
lightlevelisapproximatelylessthan1footcandleactivatingthe
LEDNightLight.Further,theinternalphotocellwillturnOFFthe
LEDNightLightwhenitdetectsanambientlightlevelover5foot
candles.TheLEDNightLighthasadjustablelightoutputtomeetthe
needs of the space and can be set to for continuous mode or dim
modewhichwillautomaticallydimto5%offullbrightnessafter2
minutesofnooccupancy.
NIGHTLIGHT DIM:ToadjusttheLEDNightLightoutput,turnthe
dialmarked“ONMODE/NLDIM”(OSSNL-INx)or“NITELITEDIM”
(OSS10)counter-clockwisetodecreaseandclockwisetoincrease
lightoutput.
NIGHTLIGHT MODE:Thefactorydefaultsettingforthe
NightLightModeisdimmedmode.ThismeanstheLEDNightLight
automaticallydimsto5%offullbrightnessafter2minutesofno
occupancywhenactivatedbytheinternalphotocell.Tochangethe
NightLightModeperformthefollowingprocedure:
1. Press and hold the push button for 2 seconds to determine the
currentmode.
a. NightLightashesonceevery1secondforContinuousMode
untilthebuttonisreleased.
b. NightLightashestwiceevery1secondforDimModeuntil
thebuttonisreleased.
2.Tochange,holdthepushbuttonfor10secondsandtheMode
willtoggle.Thiswillbeindicatedbyachangeintheashpattern
asdescribedabove.
TROUBLESHOOTING
1.Ifthereisnoresponsefromtheunit(thelightneverturnsONand
theLEDneverblinks)11/2minutesafterpowerisapplied,then
uninstalldeviceandverifythereisagroundconnectionatthe
wallbox.Ifthereisagroundconnection,verifywiring.
2.IfthelightsneverturnON,buttheLEDblinks,checkifthe
Manual-ONsetting(OSSNLonly).SeeManual-ONModesettingfor
adjustments.
3.IfthelightsconstantlystayON,evenwhentheroomisunoccupied:
A.ChecktheTimesetting.Seehowthistimecomparestohow
longthelightsstayON.
B.TryloweringtheRangeControl.Rotatetheknobcounter-
clockwiseabout30°.
C.Iftheproblempersists,tryreducingagain.
NOTE:DoNotreducesomuchthatCat.Nos.
OSSNL/OSSNL-INx/OSS10-IDxcannotseenormaloccupancy.
D.BesuretousetheBlinderstoblockanyunwanted
hallwaytrafc.
E.Checkforreectedheat/motionasSensorUnitmaybeseeing
motionthroughawindow.
F. CheckforadjacentHVACand/orheaterducts.
NOTES
Cat. No. OSSNL
T IM E
ON MODE/NL DIM
MAN
AUTO
RANGE
4
7
10
4
Blinder adjustment levers
BLINDERS
Control Panel Cover
30M
30S
1H
2H
Cat. No. OSS10
TIME
NITELITE DIM
MIN MAX
Blinder adjustment levers
BLINDERS
Control Panel Cover
10M
30S
20M
30M
RANGE
4
7
10
30S
30M
1H
2H
30secondxedtime-outforperformingawalktest
30 minute time-out
1 hour time-out
2 hour time-out
Value of TimeFace Marking
30S
10M
20M
30M
30secondxedtime-outforperformingawalktest
10 minute time-out
20 minute time-out
30 minute time-out
Value of TimeFace Marking
©2009LevitonMfg.Co.,Inc.
FCC COMPLIANCE STATEMENT
ThisdevicecomplieswithPart15oftheFCCRules.Operationis
subjecttofollowingtwoconditions:(1)thisdevicemaynotcause
harmfulinterference,and(2)thisdevicemustacceptanyinterference
received,includinginterferencethatmaycauseundesiredoperationof
thedevice.
Thisequipmenthasbeentestedandfoundtocomplywiththelimits
foraClassBDigitalDevice,pursuanttoPart15oftheFCCRules.
Theselimitsaredesignedtoprovidereasonableprotectionagainst
harmfulinterferenceinaresidentialinstallation.Thisequipment
generates,uses,andcanradiateradiofrequencyenergyand,ifnot
installedandusedinaccordancewiththeinstructions,maycause
harmfulinterferencetoradiocommunications.However,thereisno
guaranteethatinterferencewillnotoccurinaparticularinstallation.If
this equipment does cause harmful interference to radio or television
reception,whichcanbedeterminedbyturningtheequipmentOFFand
ON,theuserisencouragedtotrytocorrecttheinterferencebyoneor
moreofthefollowingmeasures:
• ReorientorrelocatethereceivingAntenna.
• Increasetheseparationbetweentheequipmentandthereceiver.
• Connecttheequipmentintoanoutletonacircuitdifferentfromthat
towhichthereceiverisconnected.
• Consultthedealeroranexperiencedradio/tvtechnicianforhelp.
FCC CAUTION
AnychangesormodicationsnotexpresslyapprovedbyLeviton
ManufacturingCo.,Inc.,couldvoidtheuser'sauthoritytooperatethe
equipment.
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
LevitonwarrantstotheoriginalconsumerpurchaserandnotforthebenefitofanyoneelsethatthisproductatthetimeofitssalebyLevitonisfreeofdefectsinmaterialsandworkmanshipundernormalandproperuseforfiveyearsfromthepurchasedate.Leviton’sonlyobligationistocorrectsuchdefectsbyrepairorreplacement,atitsoption,ifwithinsuchfiveyearperiodtheproductisreturnedprepaid,with
proof of purchase date, and a description of the problem to Leviton Manufacturing Co., Inc., Att: Quality Assurance Department, 201 North Service Road, Melville, New York 11747.Thiswarrantyexcludesandthereisdisclaimedliabilityforlaborforremovalofthisproductorreinstallation.Thiswarrantyisvoidifthisproductisinstalledimproperlyorinanimproperenvironment,overloaded,misused,opened,
abused,oralteredinanymanner,orisnotusedundernormaloperatingconditionsornotinaccordancewithanylabelsorinstructions.There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose,butifanyimpliedwarrantyisrequiredbytheapplicablejurisdiction,thedurationofanysuchimpliedwarranty,includingmerchantabilityandfitnessfora
particularpurpose,islimitedtofiveyears.Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation.Theremediesprovidedhereinaretheexclusiveremediesunderthiswarranty,whetherbasedoncontract,tortorotherwise.