Cut Sheet

Tuesday, August 24, 2004 Comparison of the Lighting Requirements of IECC.doc Page 2 of 4
Space Control 9.2.1.2 Covers:
Spaces enclosed by ceiling height partitions
Covers no more than 2,500 sq.ft per control in
spaces less than 10,000 sq.ft and no ore than
10,000 sq.ft per control in larger spaces
Requires override of no more than 4 hours
Readily accessible and can see the lighting
Allows:
Manual, or
Occupancy sensor
o Required in certain classrooms,
conference/meeting rooms and
employee lunch and break rooms if
no multi-scene control.
Exceptions:
Remote location allowed for reasons of safety
and security if has pilot light and is clearly labeled
805.2.1 Covers:
Spaces enclosed by ceiling height partitions
Within area or remote with status lights
Exceptions:
Security/emergency
Egress lighting for stairways and corridors.
Exterior Lighting
Control
9.2.1.3 Covers:
Exterior lighting when sufficient daylight is
available or when lighting is not needed
Requires:
10 hour power backup
Allows:
Photosensor (only if dusk-to-dawn operation)
Astronomical time switch
Exceptions:
Covered vehicle entrances/exits for buildings or
parking structures where required for safety,
security or for eye adaptation
805.2.3 Covers:
Exterior lighting
Allows:
Photosensor
Automatic switching
o 7-day & seasonal daylight adjustment
o 4-hour power backup
Exceptions:
24 hour operations
Additional
Controls
9.2.1.4 Covers:
Display or accent lighting
Case lighting
Hotel/Motel Guest Room Lighting
Task lighting
Nonvisual lighting
Demonstration lighting
805.2.2.3 Covers:
Guestrooms
Exceptions:
Areas with only 1 luminaire
Areas controlled by occupancy sensing
Corridors, storerooms, restrooms or public
lobbies