Cut Sheet

PRODUCT DATA
Leviton Mfg. Co., Inc. Lighting & Energy Solutions
20497 SW Teton Avenue, Tualatin, OR 97062 1-800-736-6682 Tech Line: 1-800-959-6004 Fax: 503-404-5594 www.leviton.com/les
© 2013 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
Emergency Dimming Luminaire Control
Emergency Dimming
Luminaire Control
DESCRIPTION
In the past, all designated emergency lights in
a facility had to stay on 24 hours a day to meet
safety codes. Now with Leviton Emergency
Dimming Luminaire Control, you can specify and
install a UL-924 listed emergency power control
device that can convert and control up to 20
regular light fixtures as approved emergency
lights. These emergency lights can then be
turned ON and OFF in the same manner as
regular lights.
The Emergency Dimming Luminaire Control
automatically illuminates connected emergency
loads to full brightness upon utility power
interruption, regardless of switch/dimmer
position. Ideal for emergency luminaires in public
places such as:
Auditoriums
Restaurants
Conference rooms
Theaters
Classrooms
Retail spaces
Municipal buildings
Houses of worship
FEATURES
Integral Test Switch provides convenient
anytime testing
Voltage Surge Protection ensures reliable
performance under adverse conditions
Status indicators separate LEDs indicate
regular and emergency power, allowing
verification of correct wiring connections
Emergency Power Supervision—internal
supervision circuits to prevent emergency
luminaires from illuminating during normal
times if Emergency Hot or Neutral conductors
have been interrupted. This gives warning that
a problem exists with emergency supply, which
would otherwise be unnoticed, especially
when controls are mounted above ceiling tile
Triple Safety and Reliability—consists of 2
contactors, C-1 and C-2.
- C-1 energized during normal times and
is de-energized when regular power is
interrupted
- C-2 energized when regular power is
interrupted and is de-energized when
regular power is restored
Automatically switches designated
emergency fixtures from a dimming control to
emergency power during a utility power
interruption and brings them to full brightness
Universal mounting—surface, above
suspended ceiling or recessed
Manual test switch
2-wire, 3-wire dimmable loads, including 0-10V,
DALI and Lutron EcoSystem

Summary of content (4 pages)