Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
continued from page 91
These electrical supplies shall be permitted to include 
additional receptacles that have congurations in accordance 
with 551.81. The weather-resistant requirement for 
50-ampere, 125/250-volt receptacles shall become effective 
January 1, 2026.
Informational Note: The percentage of 50-ampere sites required by 
551.71 could be inadequate for seasonal recreational vehicle sites 
serving a higher percentage of recreational vehicles with 50-ampere 
electrical systems. In that type of recreational vehicle park, the 
percentage of 50-ampere sites could approach 100 percent.
(F) GFCI Protection
(2) Receptacles Installed in Recreational Vehicle 
Site Equipment.
Ground-fault circuit-interrupter protection shall only 
be required for 125-volt, single-phase, 15 and 
20-ampere receptacles
Expert Analysis 
A revision has been accepted that covers requirements 
for 30 and 50-ampere receptacles that requires them to 
be weather-resistant and conform to Figure 551.46(C)(1) 
in the NEC. The weather-resistant requirement for 
the 50-ampere receptacles become eective   
January 1, 2026.
Leviton Note: Looking carefully at the language used in this article it 
says “shall each be equipped with a XX-amp, YYY volt weather-resistant 
receptacle” and additional receptacles are permitted as long as they 
conform to 551.81. However the article doesn’t say that these additional 
receptacles must be WR, nor does 551.81.
In addition, the WR requirement for 50 Amp takes eect Jan. 1, 2026, 
however no grace period was given for the 30 Amp receptacle.
Leviton Solution
For RV connection, Leviton oers receptacles to comply with 
requirements of Article 551.71 Weather-Resistant GFCI Receptacles
Receptacles at RV sites can take a beating. Leviton’s SmartlockPro
®
Weather-Resistant (WR) GFCI receptacles are up to the challenge. 
They are UL Listed weather-resistant to comply with Section 
551.71(A) of the National Electrical Code
®
. Constructed with UV 
stabilized thermoplastic for high cold impact resistance, the devices 
feature stainless steel straps and mounting screws. Rain or shine,
Leviton oers products to meet all your outdoor needs.
Important: Covers must be used with WR GFCI receptacles in damp 
or wet locations per NEC Section 406.9(B)(1).