FAQ
87
•  Remote monitoring — includes data like liquid accumulation,   
  enclosure temperature and humidity, line- and load-side voltage 
  values, ground continuity, and more. Access this data 24/7 and get 
  notified of any abnormal operating conditions via the Inform™ app 
  (mobile or laptop) or your existing automation system.
Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
Revision
445.19(B)(C) Emergency Shutdown of 
Generator Prime Mover 
Change Summary 
• This article separately addresses the emergency   
  generator shutdown in one-and-two family houses 
  and OTHER THAN one-and-two family houses. 
  For other than 1-or-2 family houses a remote   
  emergency stop switch to shut the prime mover shall 
  be located outside the equipment room or enclosure. 
  For 1-or-2 family houses the emergency shutdown   
  shall be located outside the dwelling unit in a readily  
  accessible location, except for cord-and-plug 
  connected generators.
Article 445 – Generators
445.19 Emergency Shutdown of Prime Mover.
(B) Remote Emergency Shutdown. For other than 
one- and two-family dwelling units, generators with 
greater than 15 kW rating shall be provided with a remote 
emergency stop switch to shut down the prime mover. The 
remote emergency stop switch shall be located outside 
the equipment room or generator enclosure at a readily 
accessible location and shall also meet the requirements of 
445.19(A)(1) and (A)(2).
The remote emergency stop switch shall be permitted to 
be mounted on the exterior of the generator enclosure. The 
remote emergency stop switch shall be labeled Generator 
Emergency Shutdown, and the label shall meet the 
requirements of 110.21(B).
(C) Emergency Shutdown in One- and Two-Family 
Dwelling Units. For other than cord-and-plug-connected 
portable generators, an emergency shutdown device shall 
be located outside the dwelling unit at a readily accessible 
location and shall also meet the requirements of 445.19(A)
(1) and (A)(2).
An emergency shutdown device mounted on the exterior 
of the generator enclosure shall be permitted to satisfy the 
requirements of this section. The shutdown device shall be 
marked as the Generator Emergency Shutdown, and the 
continued on page 88










