Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
440.11 General. Disconnecting means shall be capable of 
disconnecting air-conditioning and refrigerating equipment, 
including motor-compressors and controllers, from the 
circuit conductors. If the disconnecting means is readily 
accessible to unqualied persons, any enclosure door or 
hinged cover of a disconnecting means enclosure that 
exposes energized parts when open shall require a tool to 
open or be capable of being locked.
Expert Analysis 
A new sentence has been added to address the 
protection of unqualified persons in the vicinity of this 
equipment. Section 440.14 already addresses location.
Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
Revision
445.18(A)(B) Generator Disconnect – 
Parallel Installations and Location 
Change Summary 
• Revision clarifies the separation of an emergency   
  shutdown and a disconnecting means.
Article 445 – Generators
445.18 Disconnecting Means.
(A) Disconnecting Means. Generators other than cord-
and-plug-connected portable generators shall have one or 
more disconnecting means. Each disconnecting means shall 
simultaneously open all associated ungrounded conductors. 
Each disconnecting means shall be lockable open in 
accordance with 110.25.
The disconnecting means shall be permitted to be located 
within the generator behind a hinged cover, door, or 
enclosure panel. Where the generator disconnecting means 
continued on page 86