FAQ
83
Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
and the marking on the equipment nameplate is not less than the current 
marked on the fan or blower motor nameplate, the full-load current marked 
on the nameplate of the appliance shall be used to determine the ampacity of 
branch-circuit conductors, in addition to the current ratings of the following: 
(1) Disconnecting means 
(2) Motor controllers 
(3) Short-circuit and ground-fault protective devices 
(4) Separate overload protective devices
Exception No. 3: For a listed motor-operated appliance that is marked with 
both motor horsepower and full-load current, the motor full-load current 
marked on the nameplate of the appliance shall be used instead of the 
horsepower rating on the appliance nameplate to determine the ampacity of 
branch-circuit conductors, in addition to the current ratings of the following: 
(1) Disconnecting means 
(2) Motor controllers 
(3) Short-circuit and ground-fault protective devices 
(4) Separate overload protective devices
(2) Nameplate Values. The motor nameplate current ratings 
shall be used to determine the values for the following: 
(1) Separate motor overload protection 
(2) For motors built for low speeds (less than 1200 RPM), 
high torques, canned pumps, or multispeed motors, the 
following: 
a. Ampacity of conductors 
b. Current ratings of switches 
c. Current ratings of branch-circuit short-circuit and ground-
fault protection 
(3) Large motors exceeding the values in Part XIV shall use 
the nameplate current rating for conductor sizing.
Expert Analysis 
A revision has been made to clarify the requirements 
when applying nameplate or table values for general 
motor applications.
continued on page 84
Sizing Using Table










