FAQ
65
Revision/New
334.15(B), 334.19 Protecting Conductors 
– Bushings and Sheath Length 
Change Summary 
• The NEC has added language intended to 
  protect conductors.
Article 334 Nonmetallic-Sheathed Cable: 
Types NM and NMC
334.15 Exposed Work.
(B) Protection from Physical Damage. Cable shall be 
protected from physical damage where necessary by rigid 
metal conduit, intermediate metal conduit, electrical metallic 
tubing, Schedule 80 PVC conduit, RTRC marked with 
the sufx -XW, or other approved means. Where passing 
through a oor, the cable shall be enclosed in rigid metal 
conduit, intermediate metal conduit, electrical metallic 
tubing, Schedule 80 PVC conduit, RTRC marked with the 
sufx -XW, or other approved means extending at least 
150 mm (6 in.) above the oor. Conduit or tubing shall be 
provided with a bushing or adapter that provides protection 
from abrasion at the point the cable enters and exits 
the raceway.
Type NMC cable installed in shallow chases or grooves in 
masonry, concrete, or adobe shall be protected in accordance 
with the requirements in 300.4(F) and covered with plaster, 
adobe, or similar nish.
334.19 Cable Entries. The sheath on nonmetallic-sheathed 
cable shall extend not less than 6 mm (1/4 in.) beyond any 
cable clamp or cable entry.
Expert Analysis 
A new section has been added at 334.15 to ensure 
Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
continued on page 66










