Revision
300.14 Clarification of 6” Out of Box 
Conductors  Rule…  Spliced  or  Unspliced? 
Change Summary 
• A new sentence was added to clarify that the   
  mandatory 6 inches of conductors out of the box can 
  be spliced or unspliced.
Article 300 General Requirements for Wiring Methods 
and Materials
300.14 Length of Free Conductors at Outlets, Junctions, 
and Switch Points. At least 150 mm (6 in.) of free 
conductor, measured from the point in the box where it 
emerges from its raceway or cable sheath, shall be left at 
each outlet, junction, and switch point for splices or the 
connection of luminaires or devices. The 150 mm (6 in.) 
free conductor shall be permitted to be spliced or unspliced. 
Where the opening to an outlet, junction, or switch point is 
less than 200 mm (8 in.) in any dimension, each conductor 
shall be long enough to extend at least 75 mm (3 in.) outside 
the opening.
Exception: Conductors that are not spliced or terminated at the outlet, 
junction, or switch point shall not be required to comply with 300.14.
Expert Analysis 
A new sentence has been added to clarify that the free 
conductor is permitted to be a splice. The addition of this 
text makes that clear and free of interpretation.
Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.