FAQ
45
Revision/New
220.70 
Energy Management Systems (EMS) 
Change Summary 
• New section classifies a single value equal to the   
  maximum ampere setpoint of the energy management 
  system shall be permitted to be used in load 
  calculations for the feeder or service.
Article 220 Branch-Circuit, Feeder, and Service 
Load Calculations
220.70 Energy Management Systems (EMSs). If an energy 
management system (EMS) is used to limit the current to a 
feeder or service in accordance with 750.30, a single value 
equal to the maximum ampere setpoint of the EMS shall be 
permitted to be used in load calculations for the feeder 
or service.
The setpoint value of the EMS shall be considered a 
continuous load for the purposes of load calculations. 
Expert Analysis 
A new section has been added to address the load 
calculations of energy management systems that 
is used to limit the current to a feeder or service in 
accordance with 750.30. When performing the load 
calculations, a single value equal to the maximum 
ampere setpoint of the energy management system 
shall be permitted to be used in load calculations for 
the feeder or service.
Leviton Solution 
The first step when managing energy is to measure 
it and start a baseline. From there you can continually 
monitor energy usage to evaluate eectiveness of 
energy saving measures that you have undertaken.
Organizations can monitor, control, and manage energy
Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
VerifEye
®
 Submetering 
Code Solution
continued on page 46










