Instructions / Assembly
DI-000-CD100-00F© 2016 Leviton Mfg. Co., Inc.
1. WARNING: TO AVOID FIRE, SHOCK, OR DEATH; turn off power at circuit breaker or fuse and test that power is off before wiring!
2. Remove junction box cover plate and save screws. The Power Pack will take the place of the junction box cover (refer to Figure 1).
3. Prepare high and low-voltage wires by stripping 3/4" (1.9 cm) of insulation to expose bare copper at the end of each wire.
4. LINE VOLTAGE CONNECTIONS: Identify the voltage of your lighting circuit before attempting to install the Power Pack, either 120 or 277VAC. In accordance with local wiring
codes, connect lead wires of Power Pack per appropriate WIRING DIAGRAM as follows: Line (BLACK) lead to the Hot (BLACK) circuit conductor. Connect the Power Pack
Neutral (WHITE) lead to the Neutral (WHITE) circuit conductor. Twist strands of each lead tightly and, with circuit conductors, push firmly into appropriate wire connector. Screw
connectors on clockwise making sure that no bare conductor shows below the wire connectors. Secure each connector with electrical tape.
The Power Pack Line voltage wires exit through the back of the device and are designated as follows:
BLACK - 120VAC Line
ORANGE - 277VAC Line
WHITE - 120 or 277VAC Neutral
CAUTION: DO NOT connect both 120 and 277VAC wiring to the Power Pack at the same time, and DO NOT connect both the BLACK and ORANGE high voltage wires to the
same circuit.
5. Ensure that Power Pack Cat. No. CD100 is wired properly before mounting it back to the junction box. Carefully position all high-voltage wires in the junction box and assure that
all low-voltage wires are on the Class 2 side of the isolation barrier. Mount the Power Pack to the junction box using the cover plate screws.
6. LOW-VOLTAGE CONNECTIONS: Remove the cover plate for the low-voltage compartment. Connect the low-voltage leads of Power Pack per appropriate WIRING DIAGRAM
as follows: RED (DALI
®
) and BLACK (DALI
®
) leads to the PURPLE (DALI
®
) wires on the DALI
®
Loop. Twist strands of each lead tightly and push firmly into appropriate wire
connector. Screw connectors on clockwise making sure that no bare conductor shows below the wire connectors. Secure each connector with electrical tape.
The Power Pack Low-voltage leads exit through the side of the device, inside the isolation barrier and have polarity designations as follows:
RED - DALI
®
wire (Positive)
BLACK - DALI
®
wire (Negative)
7. Carefully position the low-voltage wires in the low-voltage compartment and replace the cover.
8. If a second CD100 DALI
®
Loop Power Pack needs to be installed, refer to Wiring Diagram 2 for parallel installation guidelines.
9. Restore power at the fuse or circuit breaker. INSTALLATION IS COMPLETE.
WHEN USING A CD250 CONTROLLER
Controller leds do not turn ON:
• Circuit breaker or fuse is OFF
- Turn the circuit breaker or fuse ON. Ensure that the lights being controlled are in working order (i.e. failed bulbs).
• Verify wiring on the DALI
®
loop
- If more than one Power Pack is installed on the same loop, check to make sure wiring of each Power Pack is polarity matched on the DALI
®
loop.
Lights will not turn ON:
• Circuit breaker or fuse is OFF.
- Turn the circuit breaker or fuse ON. Ensure that the lights being controlled are in working order (i.e. failed bulbs).
• Ensure DALI
®
ballast is functioning properly.
• Power Pack is wired incorrectly.
- Refer to the Power Pack wiring instructions.
• Check that the Controller and ballasts have been properly programmed.
- Refer to CD250 instructions.
• Measure voltage between output wires (+12V nominal)
Lights will not turn OFF:
• Power Pack is wired incorrectly.
- Check the Power Pack’s wiring.
• Ensure DALI
®
ballast is functioning properly.
• Check that the Controller and ballasts have been properly programmed. Refer to CD250 instructions.
• Check for a shorted connection on the DALI
®
loop.
INSTALLATION
Hot (Black) -120V
Hot (Orange) -277V
Neutral (White)
Line
120/277VAC, 60Hz
PURPLEPURPLE
PURPLE
PURPLE
PURPLE
PURPL
E
PURPL
E
DALI LOOP
PURPLE
PURPL
EPURPLE
CD250
DALI
CONTROLLER
CD100
DALI LOOP
POWER PACK
RED BLACK
DALI
BALLAST
DALI
BALLAST
DALI
BALLAST
PURPL
E
PURPL
E
DALI LOOP
PURPL
EPURPLE
PURPLEPURPLE
PURPLEPURPLE
PURPLEPURPLE
PURPLEPURPLE
RED BLACK
RED BLACK
Hot (Black) -120V
Hot (Orange) -277V
Neutral (White)
Line
120/277VAC, 60Hz
Hot (Black) -120V
Hot (Orange) -277V
Neutral (White)
Line
120/277VAC, 60Hz
CD250
DALI
CONTROLLER
CD250
DALI
CONTROLLER
CD100
DALI LOOP
POWER PACK
CD100
DALI LOOP
POWER PACK
DALI
BALLAST
DALI
BALLAST
DALI
BALLAST
Wiring Diagram 1 - Single Power Pack Application
NOTES:
• DALI
®
Loop wires are not polarity sensitive
• Controllers and Power Supply can be connected to any point on the DALI
®
oop