409.70 Surge Protection for Safety 
Circuits in Industrial Control Panels 
Change Summary 
• New section calls for surge protection of safety circuits  
  within control panels.
Article 409 Industrial Control Panels
409.70 Surge Protection. Safety circuits for personnel 
protection that are subject to damage from surge events 
shall have surge protection installed within or immediately 
adjacent to the control panel.
Expert Analysis 
A new section has been added to clarify that surge 
protection shall be installed within or immediately 
adjacent to the control panel to protect safety circuits 
for personnel protection. The surge protective devices 
address a documented safety issue that has been 
reported by the Electrical Safety Foundation.
Leviton Solution
51120-1 
Type 2 Single Phase Surge Panel with 4-Mode Protection
120/240V Single Phase Panel Mount 
Surge Protective Device, 4-Mode 
Protection, 50kA Max Surge Current 
Rating, NEMA 1 Enclosure, UL 1449 
4th Edition Type 2.
Leviton’s Surge Protection Devices 
can be used individually or as part of 
a coordinated application strategy, 
to protect sensitive electronic 
equipment, in industrial, commercial 
and residential locations, from the 
stress and degradation inflicted by 
voltage transients. Transients are 
diverted away from sensitive micro circuitry, providing protection 
against catastrophic failure, costly downtime and data disruptions.