NEC
®
 Text 
continued from page 109
other Class 2 circuits. Separation from other circuits shall 
comply with 725.136.
(D) Protection. Wiring shall comply with the requirements 
of 300.4 and be installed in a raceway, armored or metal-
clad cable, or cable tray.
Exception No. 1: Section 700.11(D) shall not apply to wiring that does not 
exceed 1.83 m (6 ft) in length and that terminates at an emergency luminaire 
or an emergency lighting control device.
Exception No. 2: Section 700.11(D) shall not apply to locked rooms or locked 
enclosures that are accessible only to qualied persons.
Informational Note: Locked rooms accessible only to qualied 
persons include locked telecommunications rooms, locked electrical 
equipment rooms, or other access-controlled areas.
Expert Analysis 
A new section has been added to address Class 2 
powered emergency lighting systems. Due to new 
technologies, such as power over ethernet and 
low-power consumption LED luminaires, 
these systems utilize Class 2 conductors to deliver 
power, control signals, or both from a central device 
to one or more emergency luminaires.