FAQ
107
It would not apply to an equipment room for a spa or 
hot tub, fountain, etc. An equipment room for fountain 
pumps, chlorinators, etc. is common at hotels and other 
installations. This type of equipment room should also 
have a GFCI protected receptacle. 
A GFCI protected receptable is needed for installers and 
maintainers who service equipment in these rooms.
Leviton Solution
When it comes to outdoor GFCI protection, it’s smart 
to choose SmartlockPro
®
 GFCIs.
Our large selection includes outdoor grade 
Weather-Resistant versions that are also 
tamper-resistant. Constructed with UV
stabilized thermoplastic for high cold impact 
resistance, the devices feature stainless steel 
straps and mounting screws. For the increased 
power that agricultural environments demand, 
Leviton’s 20-Amp GFCI’s are up to the test.
Important: Covers must be used with WR GFCI 
receptacles in damp or wet locations per 
NEC Section 406.9.
Cat. No. 
GFWT2-KW
Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
Revision/New
680.22(A)(4) GFCI Requirements Around 
Pool and Similar Areas Expanded 
Change Summary 
• Change expands GFCI requirements around pools to   
  include up to 250 volt receptacles.
Article 680 Swimming Pools, Fountains, 
and Similar Installations
680.22 Lighting, Receptacles, and Equipment
(A) Receptacles
(4) Ground-Fault Circuit-Interrupter (GFCI) and 
continued on page 108