AC Horsepower
Ratings
Electrical
Specifications
Environmental
Specifications
Material
Specifications
Mechanical
Specifications
Standards and
Certifications
At Rated
Voltage:
1 HP
Dielectric
Voltage:
Withstands 1250VAC
per UL 1699A
Temperature Rise
at terminals:
AFTR1/AFTR2:
Max 30°C after
250 cycles OL at
200 percent rated
current
AFRBF/AFSW1:
Max 35° C
Flammability:
Rated V-2 per UL94
Operating
Temperature:
-35°C to +66°C
Face Material:
Thermoplastic
Body Material:
Polycarbonate
Line Contacts:
Brass Double-Wipe
.031 Thick*
Terminal Screws:
Plated Steel
Grounding:
Self-Ground Clip
Grounding Screw:
Plated Steel
Yoke:
Zinc-Plated Steel
Clamps:
Brass
Terminal ID:
Brass-Hot,
Green-Ground,
Silver-Neutral
Terminal:
14-10 AWG
Product ID:
Ratings are
permanently
marked on device
Wiring:
Use with copper or
copper-clad wire.
No aluminum wiring
NEMA*:
WD-6
ANSI*:
C-73
UL498*
NOM:
003
UL1699A:
File E342815
UL Fed Spec WC-596*
CSA Standard
C22.2 No 42
CSA Technical
Information
Letter No. M-02A
*Only AFTR1 and AFTR2
General
- Use of TEST and RESET buttons is similar to traditional GFCI
receptacles of which consumers have become familiar with.
This translates into greater acceptance of the technology
and a more user-friendly platform
- Meets or exceeds UL requirements for tripping time on both
series and parallel arcs
- Device design reduces nuisance tripping
- Impact-resistant thermoplastic cover and body
- Superior resistance to electrical surges and over-voltages
- Expanded wiring options with nine back-wire holes
(two for each line and load connection plus one for ground
with an internal clamp)
- Silver alloy contacts
- Compatible with all Decora
®
devices and wallplates;
available in select colors
- Packed with coordinating wallplate (except AFRBF)
- Backed by Leviton’s Limited Two-Year Product Warranty
Lockout Action
As an additional safeguard, all Leviton AFCI Devices feature a
lockout function which prevents the device from being reset if:
- it is not functioning properly
- protection has been compromised
- line and load wires were reversed during installation
AFCI Receptacle
- Tamper-resistant to comply with the latest NEC
®
requirements for
tamper-resistant receptacles in residences and childcare facilities
Blank Face
- May be used for outlet branch circuits where AFCI protection
is desired but is located where an outlet is not needed
- Ideal for installing in locations to make AFCI protection
“readily accessible” per NEC requirements
- May be used on circuits feeding lighting loads as well as other
loads such as smoke detectors where a receptacle is not used
AFCI Switch
- Combination AFCI and single pole switch
- Use for new circuits or modifications to existing circuits
where a switch is the first outlet in a branch circuit
- Amperage: Switch 15 Amp; Receptacle 15 Amp and 20 Amp
- Voltage: 125 Volt
- Feed-through: 20 Amp protection
- NEMA: 5-15R, 5-20R
- Pole: 2
- Wire: 3
- Indicators: Reverse wiring/power
- Termination: Back & Side
- Strap Material: Galvanized Steel
- Warranty: 2-Year Limited
Key Specifications