Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
Informational Note No. 3: Areas of agricultural building 
are frequently converted to hospitality areas. These areas can 
include petting zoos, stables, and buildings used for recreation or 
educational purposes where receptacles are installed.
Exception to (1) through (10): Receptacles in the following locations shall 
not be required to be tamper resistant:
(1) Receptacles located more than 1.7 m (5 1⁄2 ft) above the oor
(2) Receptacles that are part of a luminaire or appliance
(3) Where the receptacle outlet is installed within the space occupied by or 
designated for each appliance that, in normal use, is not easily moved from 
one place to another and is cord-and-plug-connected in accordance with 
400.10(A)(6), (A)(7), or (A)(8) the following are permitted: 
a. A single receptacle that is not readily accessible and supplies one appliance 
b. A duplex receptacle that is not readily accessible and supplies two 
appliances
(4) Nongrounding receptacles used for replacements as permitted in 
406.4(D)(2)(a)
Expert Analysis 
A revision has been made to clarify the locations where 
tamper-resistant receptacles are required to be installed.
Leviton Solution
Leviton tamper-resistant receptacles, have proven 
eective in preventing electrical injuries resulting 
from foreign objects being inserted into receptacles. 
Available residential and commercial grade in 15- and 
20-Amp, 125-Volt, Duplex and Decora
®
 in several colors.