FAQ
81
Expert Analysis 
A new subsection has been added to address the 
requirements pertaining to ceiling-suspended (paddle) 
fans located in bathrooms and shower spaces.
Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
New
424.48 Requirements for Heating 
Cables in Walls 
Change Summary 
• It seems that heating cables are now being 
  installed in walls, so the NEC is addressing it with   
  new requirements.
Article 424 Fixed Electric Space-Heating Equipment
424.48 Installation of Cables in Walls. Unless prohibited 
by 424.38(B), heating cables and cable sets shall be 
permitted to be installed in, on, or behind walls provided all 
of the following are met:
(1) Heating cables and cable sets shall be identied as 
suitable for installation in, on, or behind walls.
(2) Heating cables and cable sets shall be GFCI protected.
(3) Grounding means, such as copper braid, metal sheath, or 
other approved means, shall be provided.
(4) Heating cables and cable sets shall be AFCI protected.
(5) Heating cables and cable sets shall be permitted to be 
installed no more than 1.2 m (4 ft) above the oor.
This requirement shall become effective January 1, 2026.
Expert Analysis 
A new section has been added to address the 
requirements for installation of heating cables in, 
continued on page 82