Material taken from the National Electric Code
®
 is reprinted with permission 
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022, 
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
 Text 
Revision
406.9(A)(B) While-in-Use Cover 
Requirements 
Change Summary 
• Revision made regarding how much bubble type 
  covers must open.
Article 406 Receptacles, Cord Connectors and 
Attachment Plugs (Caps)
406.9 Receptacles in Damp or Wet Locations.
(A) Damp Locations. A receptacle installed outdoors in 
a location protected from the weather or in other damp 
locations shall have an enclosure for the receptacle that is 
weatherproof when the receptacle is covered (attachment 
plug cap not inserted and receptacle covers closed).
An installation suitable for wet locations shall also be 
considered suitable for damp locations.
A receptacle shall be considered to be in a location protected 
from the weather where located under roofed open porches, 
canopies, marquees, and the like, and will not be subjected 
to a beating rain or water runoff. All 125- and 250-volt 
nonlocking receptacles shall be a listed weather-resistant 
type. Hinged covers of outlet box hoods shall be able 
to open at least 90 degrees, or fully open if the cover is 
not designed to open 90 degrees from the closed to open 
position, after installation.
Informational Note: See ANSI/NEMA WD 6–2016, Wiring 
Devices — Dimensional Specications, for the types of receptacles 
covered by this requirement.
(B) Wet Locations.
(1) Receptacles of 15 Amperes and 20 Amperes in a Wet 
Location. Receptacles of 15 amperes and 20 amperes, 125 
volts and 250 volts installed in a wet location shall have an 
enclosure that is weatherproof whether or not the attachment 
plug cap is inserted. An outlet box hood installed for this 
purpose shall be listed and shall be identied as “extra-
duty.” Other listed products, enclosures, or assemblies 
providing weatherproof protection that do not utilize an 
outlet box hood need not be identied extra duty. Hinged 
covers of outlet box hoods shall be able to open at least 90 
degrees, or fully open if the cover is not designed to open 90 
degrees from the closed to open position, after installation.
Informational Note No. 1: See ANSI/UL 514D–2016, Cover Plates 
for Flush-Mounted Wiring Devices, for extra-duty outlet box hoods. 
“Extra duty” identication and requirements are not applicable to 
listed receptacles, faceplates, outlet boxes, enclosures, or assemblies 
that are identied as either being suitable for wet locations or rated 
as one of the outdoor enclosure–type numbers of Table 110.28 that 
does not utilize an outlet box hood.
continued on page 72