Cut Sheet

Wetguard
®
Connectors
(For use with Wetguard
®
Inlets only)
NEMA & NON-NEMA
IP66 Suitability. Rated to NEMA Type 4, 4X & 12
when mated with Leviton Wetguard
®
Inlets
PK-93740-10-00-0A
WARNINGS AND CAUTIONS:
• Tobeinstalledand/orusedinaccordancewithappropriateelectricalcodesandregulations.
• Ifyouarenotsureaboutanypartoftheseinstructions,consultanelectrician.
• Usethisdevicewithstranded copper wire only.
• Non-grounded devices are for connection to non-grounded circuits only.
• Non-NEMAdevicesareULListedforreplacementuseonly.
WIRING INSTRUCTIONS
ENGLISH
TO INSTALL
NOTE:WIRESIZEANDTYPEMUSTCOMPLYWITHAPPROPRIATELOCALELECTRICALCODES.INUSAREFERTONECTABLESARTICLE400.
WARNING:TOAVOIDFIRE,SHOCKORDEATH;UNPLUG CORD OR TURN OFF POWER
ATCIRCUITBREAKERORFUSEANDTESTTHATPOWERISOFFBEFOREWIRING!
1.Selectsizeandtypeofroundcordasperyourrequirements.
2.ReferringtoFig. 1,removenut(1)fromrubberhousing(3).Separatewiringmodule(4)from
rubberhousingbypushingthemodulefrombackofhousingwithascrewdriver(orcord).
3.Selectpropersizeofstrainreliefwasher(10)andrubberbushing(9)peryourcordsizeasper
appropriate table below,orusethebackoftherubberbushingasagage.The washers and
bushings must be broken apart from each other before use (see Fig. 1).
4.Feedwiringcordthroughnut(1),strainreliefwasher(10),rubberbushing(9)andintothreaded
insertofhousing(3)asshowninFig. 1. DO NOT REVERSE ORIENTATION OF STRAIN
RELIEF WASHER AND RUBBER BUSHING.
5.Stripcordjacketandconductorsasperappropriatewire stripping gage, or as per strip gage
moldedonthebackofwiringcover.
6. Connect wires:Carefullybackoutallterminalwiringscrewsuntiledgeofbackwireclampis
notvisibleinwirewell.Twistthestrandsofeachstrippedconductortightlytogether,andinsert
intoproperwirewell.Tightenwiringscrewrmlyto12-14in.-Ibs.Torque.CHECK FOR STRAY
WIRE STRANDS. Repeat for all conductors. NOTE:Whereapplicableitisrecommendedto
connectGROUNDwirerst.
CAUTION: Wiring clamps MUST contact on conductor only, NOT on insulation.
DO NOT USE SOLID WIRE. DO NOT TIN CONDUCTORS.
7.Reattachthewiredmodule(4)tothehousing(3)byaligningkeyguide(8)onthemoduletothe
keyonthehousing,andtightentheassemblyscrewsrmlyto10-14in.-Ibs.torque.
8.Pushuprubberbushing(9)andstrainreliefwasher(10)overcordsothatthenutcanengage
the threaded insert.
IMPORTANT:Rubberhousingmustbeheldrmlywhentighteningnut.
NOTE 1: Usebackofrubberbushingsasagageforcablesizeorappropriate table below.
Alwaysusematchedbushingandstrainreliefwashers.
NOTE 2:
Polarity of wiring for NEMA devicesisidentiedbymarkingsondeviceand/orscrew
colorasshownbelow.ForPolarityofwiringforNON-NEMAdevicesrefertodevice(s)tobe
replacedforspecicwiringpattern.
1
2
3
4
A
B
C
D
5
6
7
9
10
8
Fig. 1 - Locking Connector (3 wire shown)
1 - Nut
2 - Cord
3 - Rubber Housing
4 - Wiring Module
5 - Threaded Insert
6 - Assembly Screws
7 - Terminal Screws
8 - Key Guide on Wiring Module
(to be aligned with Key on Housing)
9 - Rubber Bushing (select as per Strain Relief Washer)
10 - Strain Relief Washer
MARKING ON NEMA DEVICE
G, GRND, GREEN, or EQ GR
W, or WHITE
X,Y,Z or BLANK
CONDUCTOR COLOR
Bare, Green, or Green/Yellow wire
White or Gray wire
Black, Red, Blue or any other than White, Green, Gray, Green/Yellow or Bare wire
NEMA SCREW COLOR
(Grounding) -- GREEN
(Neutral) -- SILVER
(Hot) -- BRASS or BLACK
Wire Stripping Gage – 20A & 30A (3-5 wire) LockingWire Stripping Gage – 15A & 20A (2-3 wire) Straight Blade,
15A (2-3 wire) Locking, 20A (2 wire) Locking
Insulation
5/8"(1.6 cm)
All Conductors
1"(2.5 cm)
All Conductors except 5 wire Ground
Cord Jacket
5 Wire Ground Only
1-1/2"(3.8 cm)
15/16"
(2.38 cm)
9/16"
(1.43 cm)
Cord Jacket
Insulation