Specification

Leviton Mfg. Co., Inc. – Power Quality Division, 860 Harold Place, Chula Vista, CA 91914
• Tech line: 1-800-648-3332 • Fax: 619-205-8739
G-5379F/H1-3 M rs
© 2001 Leviton Manufacturing Co., Inc. All rights reserved.
PHYSICAL SPECIFICATIONS
Housing NEMA Type 3R steel enclosure
Physical Dimensions (approx.) 6.25" (158.8mm) x 4.25" (108.0mm) x 3.25" (82.6mm)
Mounting Flush mount into 3/4" panel knockout or use flanges to surface mount
Operating Temperature Range -10º to 60ºC
Storage Temperature Range -20º to 85ºC
Relative Humidity 5% to 95% non-condensing
Altitude Up to 3600m (11,800 ft.)
AGENCY APPROVALS:
• Listed UL 1449 Standard (2nd Edition) • CSA Certified
PRODUCT MAINTENANCE
Real-time diagnostics monitor power and surge suppression status of each phase. If protection is lost, the green LED will no longer illuminate,
red “fault” LED will illuminate, and the alarm will sound—the unit should be replaced. If unit is located where LED warning is not easily observ-
able, remote diagnostics may be used. Unit is equipped with remote-monitoring dry contacts rated 5 Amps, 120/240V AC via three, color-coded
18AWG leads rated 600V AC.
FEATURES
• Normal and common mode protection (line to neutral, line to line, and line to ground) for WYE and DELTA configured, 3-phase AC systems
(Cat. No. 32120-001 rated for 120/240V AC single-phase systems)
• Real-time diagnostics monitor power and suppression status for each phase and provide both LED indicators and an audible alarm.
• Equipped with dry contacts for remote diagnostics
• Compatible with Leviton’s Decora Home Controls powerline carrier products
32000 Series
.........................
Panel Mounted Multi-Phase Surge
Protective Device (SPD)
Cat. No. Rating MCOV* (L-N) MCOV* (L-L) Max. Single-Pulse Max. Single-Pulse
Operating Frequency Transient Energy Surge Current
@ 50, 60Hz per phase (10x1000µs) NM/CM per phase
Joules (8x20µs)
32120-001 120/240V AC single-phase 150 270 720 80kA
32120-DY3 120/208V AC 3-phase WYE, 150 270 1440 80kA
220V AC 3-phase DELTA
32277-DY3 277/480V AC 3-phase WYE, 320 540 2560 80kA
220/380V AC 3-phase WYE,
240V AC 3-phase DELTA,
480V AC 3-phase DELTA
32347-DY3 347/600V AC 3-phase WYE 420 660 3640 80kA
32412-DS3 120/240V AC Hi-Leg, 150 250 1210 80kA
Split-Phase DELTA
PERFORMANCE SPECIFICATIONS
CLAMPING PERFORMANCE
Specification 32120-001 32120-DY3 32277-DY3 32347-DY3 32412-DS3
L-N/L-L/N-G L-N/L-L/N-G L-N/L-L/N-G L-N/L-L/N-G L-L/HiL-G/L-N(CT)/HiL-N
Cat. B3 combination wave 532/832/514 532/832/514 996/1570/920 1100/2200/1100 925/1250/520/725
(6kV/3kA) peak clamping
voltage
UL 1449 Suppressed Voltage 500/700/500 500/700/500 900/1500/800 1200/2000/1000 800/1000/400/700
Ratings (SVR)
*Maximum Continuous Operating Voltage
Suppressed Voltage Ratings (SVR) assigned at 6-inch lead length with 6kV/500A impulse in accordance with UL 1449 (2nd Edition)
EM1/RFI NOISE REJECTION
All Cat. No. 32000 SPD’s Normal Mode Common Mode
Evaluation Bandwidth 300kHz – 1.2MHz 300kHz – 1.2MHz
Noise Rejection @ 50 Ohms -20dB -20dB