Diagnostics and troubleshooting
Leuze electronic RSL 410 83
I0719 Timeout of signals RES1 or RES2 (acknowl-
edgment button, start/restart).
Check the wiring of inputs RES1 and RES2.
The time specifications for start/restart must
be observed.
P0747 Safety configuration is not compatible: pro-
tective/warning field radius too small.
Change the dimensions and contour of the
protection field in the configuration. The min-
imum range of the protection field must be
observed.
I0825 Simulation mode has been activated. The safety-related switching outputs
(OSSDs) have been switched off.
I0826 Simulation mode has been deactivated. The sensor is again in safety mode.
CAUTION!
Be aware of potential hazards which can
occur when the machine is started up!
F.... The monitoring functions have detected an
internal error.
Create the service file (see chapter 4.5.5
"DIAGNOSIS")and contact the
Leuze electronic customer service (see
chapter 14 "Service and support").
Diagnos-
tic ID
Diagnostics message Measure