Datasheet
Diagnostics and troubleshooting
Leuze electronic RSL 410 82
U0575 Switching fault, EDM at OSSD A: external
relay does not switch on.
Check the wiring of the downstream relays
and that they are functioning correctly.
U0576 Switching fault, EDM at OSSD B: external
relay does not switch off.
Check the wiring of the downstream relays
and that they are functioning correctly.
U0577 Switching fault, EDM at OSSD B: external
relay does not switch on.
Check the wiring of the downstream relays
and that they are functioning correctly.
U0580 Switching fault at inputs SE1 and SE2; exter-
nal safety device does not switch in accor-
dance with the specifications.
Check the wiring of the external safety
device and that the parameter settings in the
configuration are correct.
U0582 Field pair changeover is not performed in
accordance with the specifications config-
ured in the safety sensor: overlap time too
long.
Check the changeover times of function
inputs F1 to F10 or the parameter settings in
the configuration.
U0583 Field pair changeover is not performed in
accordance with the specifications config-
ured in the safety sensor: no signal for field
pair activation.
Check the wiring and the changeover times
of function inputs F1 to F10.
U0584 Field pair changeover is not performed in
accordance with the specifications config-
ured in the safety sensor: changeover time
exceeded.
Check the changeover times of function
inputs F1 to F10 or the parameter settings in
the configuration.
U0585 Field pair changeover is not performed in
accordance with the specifications config-
ured in the safety sensor: changeover order
not observed.
Check the wiring of function inputs F1 to F10
and that the parameter settings in the config-
uration are correct.
E0588 Optics cover is soiled. Clean the optics cover. Restart the safety
sensor.
I0604 Optics cover is soiled. Clean the optics cover as soon as possible.
Sensor is still in safety mode.
P0653 Safety configuration is not compatible: pro-
tective/warning field radius too large.
Swap out the safety sensor or change the
configuration. The type of safety sensor
must be the same as the type stored in the
connection unit or in the
Sensor Studio
soft-
ware.
P0654 Field pair changeover is not performed in
accordance with the specifications config-
ured in the safety sensor: field pair not
defined.
Check the wiring of function inputs F1 to F10
and that the parameter settings in the config-
uration are correct.
I0660 Field pair changeover is not performed in
accordance with the specifications config-
ured in the safety sensor: no field pair acti-
vated at system start.
Check the wiring of function inputs F1 to F10
and that the parameter settings in the config-
uration are correct.
U0661 Safety-related switching outputs (OSSDs)
cannot be switched: short circuit with 0 V,
+24 V DC or between OSSDs.
Check the wiring of the OSSDs.
Diagnos-
tic ID
Diagnostics message Measure