Datasheet
Specifications
24 MA 248i Leuze electronic
5 Specifications
5.1 General specifications
Electrical data
Interface type 2x PROFINET-IO, integrated switch,
BUS: 2x M12 socket (D-coded)
PWR/IO: 1x M12 connector (A-coded), 1x M12 socket
(A-coded)
Protocols PROFINET-IO RT-communication
DCP
TCP/IP (firmware upload via web server)
ARP
PING
Baud rate 10/100MBaud
Data formats Data bit: 8, parity: None, stop bit: 1
Service interface RS 232, 9-pin Sub-D connector, Leuze standard
Switching input/output 1 switching input/1 switching output
device-dependent voltage
Operating voltage 18 … 30VDC (PELV, Class 2)
1)
Power consumption Max. 5VA (without DEV, current consumption max.
300mA)
Max stress on the connector
(PWR IN/OUT)
3A
Indicators
LED LINK0 green Connection possible
yellow RX/TX0 data transmission
LED LINK1 green Connection possible
yellow RX/TX1 data transmission
BF LED red Bus error
SF LED red Collection error
Mechanical data
Protection class IP 65 (with screwed-on M12 and connected Leuze
device)
Weight 700 g
Dimensions (HxWxD) 130 x 90 x 41mm / with plate: 180 x 108 x 41mm
Housing Diecast aluminum
Connection 2 x M12: BUS IN / BUS OUT PROFINET-IO
1 connector: RS 232
1 x M12: Power IN/GND and switching input/output
1 x M12: Power OUT/GND and switching input/output
Environmental data
Operating temperature range 0°C … +55°C
Storage temperature range -20°C … +60°C
Air humidity Max. 90% rel. humidity, non-condensing