Datasheet
Specifications for Leuze end devices
98 MA 248i Leuze electronic
16.11 BPS 300i bar code positioning system, ODSL xx optical distance sen-
sors with RS 232 interface (S4 switch position B)
Notice!
In this switch position, 6-byte data (fixed) is always expected by the device. This is why a
quick telegram sequence can be transmitted reliably even without a data frame.
BPS 300i
Specifications for the serial interface
Specifications for Command mode
To activate the Command mode, bit 0 must be set to 1 in control byte 0.
For further information, see chapter 11.1.3 "Command mode", figure 11.2.
Recommended settings
• Input module: 8 bytes
• Output module: 8 bytes
Default parameter BPS 300i
Baud rate 38400
Data mode 8N1
Handshake no
Protocol binary protocol without acknowledgment
Frame <Data>
Control bit Meaning Corresponds to
serial command
(ASCII)
0 Transmit individual position value = single shot C0F131
1 Cyclically transmit position values C0F232
2 Stop cyclical transmission C0F333
3 Laser diode on C0F434
4 Laser diode off C0F535
5 Transmit single speed value C0F636
6 Cyclically transmit speed values C0F737
7 Transmit single position and speed value C0F838
8 Cyclically transmit position and speed values C0F939
9 Transmit marker information C0FA3A
10 Not used / reserved
11 Transmit diagnostic information C0FC3C
12 Activate standby C0FD3D
13
14
15