Install Instructions
Home Screen: Current outlet temperature and Set point temperature
6
The user is returned to the ‘Home Screen’ which displays current temperature as measured on
valve outlet and the set point temperature on the line below.
Note: A large negative value displayed at the Cur temp line indicates the sensor is damaged or
not properly wired to the main control board.
Note: Pressing the ▲ key will reverse the order previously shown and allow the user to scroll
through the above menu items in reverse order.
Calibration Screen 2: Full Valve Sweep Counts
The above Calibration Screen is used to enter the initial Full Valve Sweep Value obtained and recorded
in Step #10 from initial power up. Press ENTER to input FVS value, it will flash. Use ▲ button to adjust
FVS counts value and advance until it agrees with the Initial Sweep Value recorded in Step #10 above.
Press ENTER to save the FVS counts value. To Exit Calibration: Press the ▲▼buttons simultaneously.
This will return you to the HOME Screen: