Install Instructions
3
REMEMBER! THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED
AND MAINTAINED ON A REGULAR BASIS. (SEE MAINTENANCE GUIDE
AND RECORD, MGR-1000).
INSTALLATION CONTINUED
ITEM:
PROBLEM:
RECOMMENDED
REPAIR KITS
PACKINGS &
GASKETS
1. Leak at stem.
2. Leak between valve cover and base.
KIT 1/XL32
SHUTTLE
ASSEMBLY
3. Valve delivers either all hot or all cold water, or will not mix consistently.
KIT R/LV981
CHECKSTOPS
4. Hot water bypass into cold line.
5. Supplies cannot be shut off completely.
6. Leak at checkstop bonnet.
KIT 4/M20
Leonard Type LV Thermostatic Water Mixing Valves are
simple in design and may be easily cleaned, adjusted and
repaired. If the installation is accessible, servicing may be
completed without disconnecting the valve.
NOTE: Thermostatic Water Mixing Valves are
REGULATING mechanisms, which must be regularly
maintained to provide best performance. Frequency of
cleaning depends on quality of local water conditions and
usage. (See Maintenance Guide and Record MGR-1000).
TROUBLESHOOTING INSTRUCTIONS
SERVICE
WARNING
WARNING! This Thermostatic Mixing Valve has an Locking Temperature Regulator (LTR) which
must be checked. If the temperature is too high, the installer MUST RESET this adjustment
immediately. Always check the temperature of the mixed water after installation. Excessively hot
water is DANGEROUS AND MAY CAUSE SCALDING!