User Manual

9400 Technology applications | Positioning sequence control
Parameter setting & configuration
Parameterisable function blocks
72 L EDS94TA10060xxxx EN 1.2 - 03/2010
5.14.8 L_PosSequencer1
Is an instance of Function
L_PosSequencer Sequence control
Program flow
( 32)
Note!
The parameters of the different actions for the sequence table are described in
the chapter "Overview of action types
". ( 33)
Parameter Possible settings Information
C04500/1...100 Sequence table
The calls of the actions required
for the positioning program are
stored in the subcodes.
In this way, the basic process
sequence (except for branches) is
described.
0Program end
xxyyy Action call
•xx action type
yyy action number
C04501 1 100 Current program step
•Read only
C04502 State of sequence control
•Read only
0 READY: Positioning program ready
to start/program end reached.
1 RUN: Positioning program is
running.
2 PAUSE: Current step interrupted,
pause is active.
3 BREAK: Positioning program
interrupted.
4 RESET: Positioning program reset.
C04503 Sequence control
Bit-coded code for sequencer
control via a PC or a higher-level
control by means of the
parameter channel.
Setting a bit to "1" activates the
corresponding function.
Bit 0 Start
Bit 1 Pause
Bit 2 Break
Bit 3 Cancel
Bit 4 Reset
Bit 5 NextStep
C04504 Program step for abort
This step is processed when the
input bCancel is set to TRUE.
0 Sequence step
1...100 Step 1 ... 100
101 Program end
C04505 Text Current comment
•Read only