Owner manual
9400 HighLine | Parameter setting & configuration
Diagnostics & error analysis
Error messages of the operating system
476 Firmware 1.37 - 09/2006 L
Electronic nameplate: Unknown encoder signal [0x007b0033]
Internal communication error (DMA) [0x007b0034]
Internal communication error (MCTRL host) [0x007b0036]
Invalid PLC configuration [0x007b0037]
Motor parameter identification has been cancelled [0x007b0038]
Electronic nameplate: Data out of parameter limits [0x007b0039]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause Remedy
The connected motor with feedback is not supported by
the controller firmware.
Check drive dimensioning.
Response (Lenze setting printed in bold)
None : System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error. Please contact Lenze.
Response (Lenze setting printed in bold)
None : System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error. Please contact Lenze.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
An invalid control configuration has occurred. Load other application.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The motor current during identification was too high. • The motor must not move during identification.
• Check motor parameters
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
Cause Remedy
The motor parameters of the electronic nameplate are
out of the limit values of the controller and therefore
cannot be accepted.
Please contact Lenze.