Error messages of the operating system
464 Firmware 1.37 - 09/2006 L
DC-bus capacitor: Temperature > CXXXXX [0x00770004]
DC-bus capacitor: overtemperature [0x00770005]
Inside the device: Temperature > CXXXXX [0x00770006]
Inside the device: Overtemperature [0x00770007]
CPU: Temperature > C00126 [0x00770008]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked : Warning Information
Cause Remedy
Electrolytic capacitor temperature higher than warning
threshold.
Check control cabinet temperature.
Clean filter.
Clean controller.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Electrolytic capacitor temperature higher than limit
temperature (120 °C).
Check control cabinet temperature.
Clean filter.
Clean controller.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked : Warning Information
Cause Remedy
Inside temperature higher than warning threshold. Check control cabinet temperature.
Clean filter.
Clean controller.
Response (Lenze setting printed in bold)
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Inside temperature higher than limit temperature (85
°C).
Check control cabinet temperature.
Clean filter.
Clean controller.
Response (Lenze setting printed in bold) Setting: C00589 (; Adjustable response)
: None System fault ; Fault Trouble Quick stop by trouble Warning locked ; Warning Information
Cause Remedy
CPU temperature higher than variable limit temperature
(C00126
).
Controller ambient temperature too high.
Dirty fan or ventilation slots.
Value set under C00126 is too low.
Check control cabinet temperature.
Clean filter.
Clean controller.
Set a higher value under C00126
.