5 Function blocks
5.165 L_TbDeadband - dead band with gain
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.165 L_TbDeadband - dead band with gain
This FB produces a symmetrical dead band around zero.
The attenuation of the input signal caused by the dead band can be compensated by a parame-
terisable gain.
The value output to output dnOut is internally limited to ±2
31
-1.
•The bLimitActive output displays if a limitation is active.
The function corresponds by approximation to the "DB" function of the 9300 servo inverter.
Inputs
Outputs
Parameter
Function library: LenzeToolbox
Runtime software licence: Motion Control HighLevel Motion Control TopLevel
Identifier/data type Information/possible settings
dnIn
DINT
Input signal
dnDeadband
DINT
Dead band area for the input signal
Value is internally limited to 0.
Identifier/data type Value/meaning
dnOut
DINT
Output signal
•If |dnIn| dnDeadband the output is set to zero.
•If |dnIn| > dnDeadband the difference multiplied by the parameterised gain is
output as output signal.
The sign results from the sign of dnIn and the sign of the selected gain.
Internally limited to ±2
31
-1
bLimitActive
BOOL
Output signal within the limitation
TRUE The output signal dnOut is limited.
Parameter Possible settings Information
C04065 -214748.3647 214748.3647 Gain
Initialisation: 1.0000
GQ2XW
E/LPLW$FWLYH