5.140 L_SdSpeedSet - setpoint ramp generator
528
Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.140.1 Setpoint path
The signals in the setpoint path are limited to ±200.00 % of the motor Motor reference speed
(C00011).
The signal at dnSpeedSetpointIn_n is first led via the function "Selection of fixed setpoints".
A selected fixed setpoint switches the input dnSpeedSetpointIn_n inactive and the subsequent
signal conditioning uses the selected fixed setpoint.
By setting the input bInvertSetpoint to TRUE the input signal of the ramp generator can be in-
verted.
5.140.2 Fixed setpoints
In addition to the direct setpoint selection via the input dnSpeedSetpointIn_n fixed setpoints can be
preset in C04200/1...15.
These fixed setpoints can be called binary coded any time via the selection inputs bJog1 ... bJog8,
so 15 options are available.
The number of selected inputs to be assigned depends on the number of required fixed set-
points.
Selected inputs Used
Setpoint
bJog8 bJog4 bJog2 bJog1
FALSE FALSE FALSE FALSE dnSpeedSetpointIn_n
FALSE FALSE FALSE TRUE C04200/1
FALSE FALSE TRUE FALSE C04200/2
FALSE FALSE TRUE TRUE C04200/3
FALSE TRUE FALSE FALSE C04200/4
FALSE TRUE FALSE TRUE C04200/5
FALSE TRUE TRUE FALSE C04200/6
FALSE TRUE TRUE TRUE C04200/7
TRUE FALSE FALSE FALSE C04200/8
TRUE FALSE FALSE TRUE C04200/9
TRUE FALSE TRUE FALSE C04200/10
TRUE FALSE TRUE TRUE C04200/11
TRUE TRUE FALSE FALSE C04200/12
TRUE TRUE FALSE TRUE C04200/13
TRUE TRUE TRUE FALSE C04200/14
TRUE TRUE TRUE TRUE C04200/15
Number of the fixed setpoints required Number of the selection inputs to be assigned (bJog1 ... bJog8)
1 at least 1
1 ... 3 at least 2
4 ... 7 at least 3
8 ... 15 4