User guide
Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05 489
5 Function blocks
5.130 L_SdMotorPot - motor potentiometer
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Outputs
Parameter
Identifier/data type Value/meaning
dnOut_n
DINT
Output value in [%]
• Display parameter: C04368
bLimitActive
BOOL
Status signal "Output value is limited"
TRUE The output value dnOut_n lies on a limit value or lies beyond the li-
mit values and is directed to the nearest limit value.
Parameter Possible settings Information
C04360/1 -200.00 % 200.00 Upper limit value
• Initialisation: 200.00 %
C04360/2 -200.00 % 200.00 Lower limit value
• Initialisation: -200.00 %
C04361/1 0.001 s 999.999 Acceleration time
• Relating to a change of the output
value by 100 %.
• Initialisation: 10 s
C04361/2 0.001 s 999.999 Deceleration time
• Relating to a change of the output
value by 100 %.
• Initialisation: 10 s
C04362
The output value dnOut_n
Deactivation function
•Behaviour of dnOut_n if bDisable
is set to TRUE.
0 ...maintains its last value. Lenze setting
1 ...is increased to 0 % with the decele-
ration time or increased with the ac-
celeration time.
2 ...is increased to the lower limit va-
lue with the deceleration time.
3 ...is increased to the upper limit va-
lue with the acceleration time.
11 ...is set to 0 % immediately
. Important for the emergency stop
function
12 ...is set to the lower limit value im-
mediately.
13 ...is set to the upper limit value im-
mediately.
C04363
The output value dnOut_n
Initialisation function
•Behaviour of dnOut_n after mains
connection.
0 ...is set to its last value before mains
switch-off.
Lenze setting
1 ...is set to 0 %.
2 ...is set to the lower limit value.
3 ...is set to the upper limit value.
C04368 -200.00 % 200.00 Output setpoint
•Display of the dnOut_n output va-
lue.










