5.99 L_LdVirtualMasterP - virtual master for synchronism
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.99.1 Functions
Handwheel function
Ensures an easy control of a machine run. The clutched drives are interconnected in a system.
Incremental encoders via DFIN or multiple encoder input. An input must be selected.
No ramp functions are active.
Function is enabled via the control (PLC) by selecting the "handwheel function" operating mode
(C05010 ="2") and setting bEnable to TRUE.
Manual jog (inching)
Operation per HMI or keys via control (PLC). The locking is done in the PLC.
Ramp functions are active.
Parameters are defined once or changed via HMI.
Single cycle
Operation per HMI or keys via control (PLC)
Function starts with a FALSETRUE edge at the bCycle input.
Ramp functions are active.
The data for production speed are used as parameters.
The cycle starts at the current position and stops at the stop position (C05011).
Continuous operation
Operation per HMI or keys via control (PLC)
Function starts with a FALSETRUE edge at the bContinuous input. The function remains active
as long as the TRUE level is applied.
Ramp functions are active.
The data for production speed are used as parameters.
The cycle starts at the current position and stops at the stop position (C05011).
Synchronise virtual master to the external master
The virtual master is synchronised to an external position selection. Thus, the downstream
system can be separated from the external master any time.
Application: Modular machines: The external position is delivered by
MotionBus (Slave)
DFIN/multiple encoder input/FB L_LdSetXAxisVelocity (relative synchronism)
Fieldbus as real encoder (must be limited to the cycle set).
The function is activated by setting bEnable to TRUE.