User guide

5 Function blocks
5.74 L_DevReadParDInt - reading parameters of the DINT type
278
Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Outputs
Parameters
Identifier/data type Value/meaning
dnState
DINT
Status (bit coded)
Bits that are not listed have not been assigned with a status (always "0").
Bit 0 Read request has been sent to the operating system and the FB is
waiting for a response from the device addressed (signal bBusy).
Bit 1 Read request has been executed correctly (signal bDone).
Bit 15 Error (group signal for bit 16 ...31).
Bit 16 Configuration error: Invalid code.
Bit 17 Configuration error: Invalid subcode.
Bit 19 Configuration error: Invalid target address.
Bit 20 Time-out error: The addressed device did not respond within the
time-out time, the read request has been deleted.
Bit 22 Error: Limit value has been exceeded.
Bit 23 Error: Parameter reading is not permitted.
Bit 24 Error: Access is not permitted.
Bit 25 Error: No element of selection list.
bBusy
BOOL
Status output "Read request transmitted"
TRUE The read request has been sent to the operating system and the FB is
waiting for a response from the device addressed.
TRUEFALSE The read request has been completed.
bDone
BOOL
Status output "Read request executed correctly"
The output remains set until bExecute is reset to FALSE (however, at least for one
task cycle).
TRUE The read request has been executed correctly and the read parame-
ter value is available at the output dnData.
bError
BOOL
Status output "Error"
TRUE An error has occurred during processing.
For details, please see the status output dnState.
dnData
DINT
Parameter value read
Parameter Possible settings Info
C05910 0 12000 Code
•Initialisation: 2
C05911 0 255 Subcode
•Initialisation: 0
C05912 Interface
Currently, only the Lenze setting
"Own device" is supported.
1Own device
2CAN on-board
3Module in MXI1
4Module in MXI2
C05913 0 128 Target address
Selection of parameter channel
for target device.
Setting is only required if an exter-
nal parameter is to be read
(C05912 > "1").