Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05 145
5 Function blocks
5.2 L_CamContactor - cam group with switch-on and switch-off dynamisation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Position-time cams in positive effective direction
If the input position dnPosIn_p reaches the cam switch-on position in positive effective direction,
the output bOut is set to TRUE and is only reset to FALSE after the time defined has elapsed.
Once the output is set to TRUE, a following change in direction has no impact on the cam signal.
[5-6] Example: Position-time cams in positive effective direction
Position-time cams in negative effective direction
If the input position dnPosIn_p reaches the cam switch-on position in negative effective direction,
the output bOut is set to TRUE and is only reset to FALSE after the time defined has elapsed.
Once the output is set to TRUE, a following change in direction has no impact on the cam signal.
[5-7] Example: Position-time cams in negative effective direction
V
t
t
dnPosIn_p
bOut
t
on
0
t t
V
t
t
dnPosIn_p
bOut
t
on
0
t t