Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013 37
Data transfer
Data transmission slave 2 (AS-i profile 7.A.E)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Accessing the parameter bits
Parameter bits P0 ... P3 provide diagnostic information to the master for slave 2. Here, P0 ... P2
define whether a status query of code C00150 or an error/warning diagnostics is returned as slave
response to the master.
The values of P0 ... P3 are transmitted to the master via the "Write_Parameter" command.
Error messages and warnings
Bits Signal / I/O mapping Description
P0 Diagnostic information
(slave master):
4 status bits of the status word
C00150
Error messages / warnings (see
below)
Values P0 - P1 - P2:
• 0 - 0 - 0: Query C00150/Bits 0 ... 3
• 0 - 0 - 1: Query C00150/Bits 4 ... 7
• 0 - 1 - 0: Query C00150/Bits 8 ... 11
• 0 - 1 - 1: Query C00150/Bits 12 ... 15
• 1 - 0 - 0: Active error
• 1 - 0 - 1: Active warning
P1
P2
P3
Note!
No error message / warning is ever provided other than the one with the highest priority.
As long as this error message / warning is pending, no other can be provided.
Values Error message Warning
P0 P1 P2 P3
0 0 0 0 No failure No warning
0001"OC1" - Short circuit "OC5" - Device load warning
0010"OC2" - Ground fault "OC6" - Overload warning
0011 "OH" - High temperature Heat sink temperature high warning
0 1 0 0 "US02" - User error #1 "US01" - User warning #1
0 1 0 1 "OU" - High bus voltage Brake resistor overload
0 1 1 0 "LU" - Low bus voltage error "LU" - Low bus voltage warning
0 1 1 1 "OC6" - Overload error Motor identification active
1 0 0 0 "Su02" - Single phasing "Su02" - Single phasing
1 0 0 1 "US02" - User error #2 "US02" - User warning #2
1 0 1 0 "dbF" - Dynamic brake fault AutoStartLock
1 0 1 1 "PS0x" - EPM failure Motor phase failure
1 1 0 0 "DF0x" - Internal failure AIN current < 4 mA
1101"OH3" - PTC fault Reserved (unused)
1 1 1 0 Drive Unit "offline" Reserved (unused)
1111Other failure Other warnings