4 Technical data
General data and operating conditions
EDK84AZESRx DE/EN/FR/ES/IT 2.0
46
l
H1_Daten−FE−Filt_84_Abmess_Tab
Operating conditions
Ambient conditions
Climatic
Storage IEC/EN 60721−3−1 1K3 (−25 ... +55 °C)
Transport IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)
Operation IEC/EN 60721−3−3 3K3 (−10 ... +55 °C)
Permissible
humidity
EN 61800−2 Humidity class 3K3 (without condensation;
average relative humidity 85 %)
Pollution EN 61800−5−1 Degree of pollution 2
Site altitude < 4000 m amsl
Above 1000 m amsl reduce the power by
5 %/ 1000 m.
Mechanical
Vibration resistance (9.81 m/s
2
= 1 g)
Transport
IEC/EN 60721−3−2 2M2
EN 61800−5−1
2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to
15 m/s
2
Operation
Germanischer Lloyd 5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
EN 61800−5−1
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 10 m/s
2
Electrical
Mains connection
Power system
TT, TN (with earthed neutral) Operation is permitted without any restrictions.
IT Operation is not permissible.
Mounting conditions
Mounting place
In the control cabinet
Mounting position Vertical
Free space ^ 51